Microprocessor Controller for DOAS
47
®
Binary Values - Read Only
Occupied
Occupied Status.
Occupied
Unoccupied
16
BV
ReadCOV_
NoWrite
0
10002
Discrete
Unoccupied
Unoccupied Status.
Unoccupied
Occupied
17
BV
ReadCOV_
NoWrite
0
10003
Discrete
Unoccupied_Cooling_
Call
Unoccupied Cooling Call
Status
Active
Inactive
18
BV
ReadCOV_
NoWrite
0
10004
Discrete
Unoccupied_
Dehumidification_Call
Unoccupied
Dehumidification Call
Status
Active
Inactive
19
BV
ReadCOV_
NoWrite
0
10005
Discrete
Unoccupied_Heating_
Call
Unoccupied Heating Call
Status
Active
Inactive
20
BV
ReadCOV_
NoWrite
0
10006
Discrete
Occupied_Start
Occupied Start Command
Status
Active
Inactive
21
BV
ReadCOV_
NoWrite
0
10007
Discrete
Unoccupied_Start
Unoccupied Start Command
Status
Active
Inactive
22
BV
ReadCOV_
NoWrite
0
10008
Discrete
Enable_Controls
Status to indicate startup
is complete and the unit is
ready.
Enabled
Disabled
23
BV
ReadCOV_
NoWrite
0
10009
Discrete
Global_Alarm
General alarm point.
Optionally set to indicate
any alarm is active, or a
shutdown alarm is active.
Alarm
Normal
24
BV
ReadCOV_
NoWrite
0
10010
Discrete
System_Shutdown_
Alarm
Shutdown alarm status.
When true, System Enable
will be set to false and the
unit will remain off.
Shutdown
Normal
25
BV
ReadCOV_
NoWrite
0
10011
Discrete
Damper_Open
Indicates there is a open
air path and the supply fan
can run.
Open
Closed
26
BV
ReadCOV_
NoWrite
0
10012
Discrete
Cooling_is_On
Indicates that the unit is
cooling.
Active
Inactive
27
BV
ReadCOV_
NoWrite
0
10013
Discrete
Economizer_is_On
Indicates that the unit is
economizing.
Active
Inactive
28
BV
ReadCOV_
NoWrite
0
10014
Discrete
Heating_is_On
Indicates that the unit is
heating.
Active
Inactive
29
BV
ReadCOV_
NoWrite
0
10015
Discrete
Dehumidification_
Mode_Enabled
Indicates that the unit is
dehumidifying.
Active
Inactive
31
BV
ReadCOV_
NoWrite
0
10017
Discrete
Manual_Override_
Active
Indicates that manual
overrides are active.
Override
Normal
32
BV
ReadCOV_
NoWrite
0
10018
Discrete
Cooling_Not_Locked_
Out
Indicates that cooling is
allowed.
Allowed
Locked_
Out
33
BV
ReadCOV_
NoWrite
0
10019
Discrete
Heating_Not_Locked_
Out
Indicates that heating is
allowed.
Allowed
Locked_
Out
34
BV
ReadCOV_
NoWrite
0
10020
Discrete
Preheat_Not_Locked_
Out
Indicates that preheat is
allowed.
Allowed
Locked_
Out
36
BV
ReadCOV_
NoWrite
0
10022
Discrete
HGRH_Purging
Indicates that the hot gas
reheat value is purging.
Active
Inactive
37
BV
ReadCOV_
NoWrite
0
10023
Discrete
Allow_Dampers
Startup sequence command
to open dampers
Yes
No
43
BV
ReadCOV_
NoWrite
0
10029
Discrete
Allow_Exhaust_Fans
Startup sequence command
to trigger exhaust fans to
start
Yes
No
44
BV
ReadCOV_
NoWrite
0
10030
Discrete
Allow_Supply_Fans
Startup sequence command
to trigger supply fans to
start
Yes
No
48
BV
ReadCOV_
NoWrite
0
10034
Discrete
BMS_Watchdog_Active
Status of the BMS
watchdog ping.
Active
Inactive
49
BV
ReadCOV_
NoWrite
0
10035
Discrete
BMS_Occupancy_
Status
Status of the BMS
occupancy command.
Occupied
Unoccupied
50
BV
ReadCOV_
NoWrite
0
10036
Discrete
Compressor_1_
Enable_Digital_Output
Compressor 1 Enable
Digital Output
Active
Inactive
111
BV
ReadCOV_
NoWrite
0
10164
Discrete
Compressor_2_
Enable_Digital_Output
Compressor 2 Enable
Digital Output
Active
Inactive
112
BV
ReadCOV_
NoWrite
0
10165
Discrete
Compressor_3_
Enable_Digital_Output
Compressor 3 Enable
Digital Output
Active
Inactive
113
BV
ReadCOV_
NoWrite
0
10166
Discrete
Appendix: Points List
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST
INDEX
REGISTER
TYPE
SIZE