Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
PIR Sensitivity
1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
3. Stand still three to four feet away from sensor for five seconds. LED should not turn ON.
4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.
Field-of-view outside the space
1. Adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.
2. Use non-reflective tape strips to cover the portions of the sensor lens that view outside the space.
Daylight Adjustments
The daylighting feature prevents the lights from turning ON when the room is adequately
illuminated by natural light. If there is enough light in the room regardless of occupancy,
the sensor will hold the lights OFF. If there is not enough light in the room, the sensor will
allow the lights to turn ON when occupied. The sensor will not allow the daylighting feature
to turn the load OFF until the space is vacant or the light level rises above the setpoint and
the Time Delay expires. While in Manual Activation Mode, if someone attempts to turn the
load ON and there is sufficient daylight available the Daylighting feature will hold the lights
OFF.
1. Set the light level when the ambient light is at the level where no artificial light is
needed. If this feature is not needed,leave the light level at maximum (fully CW).
2. With the load(s) ON, put the sensor into Test Mode. To place into Test Mode, toggle
DIP Switch 8 out of its current position, wait 3 seconds and then back in to its
original position.
3. Set the Light level to minimum (fully CCW).
4. Let the sensor Time-out so lights are OFF. Enter the space and lights should remain
OFF.
5. Make sure not to block the sensor from the daylight source and adjust the light level
potentiometer CW in small increments. (Pause 5 seconds between each adjustment).
6. Lights will not turn ON upon occupancy activation, when the ambient light level exceeds the daylight threshold setting.
Time Delay Adjustments
People who remain very still for long periods of time may need a longer
Time Delay than the default setting of 10 minutes. As long as the self-
adjusting feature is enabled, the switch will respond to each pair of False-offs
with no normal OFF in between, by alternately making slight adjustments to
either Time Delay (by 2 minute increments) or sensitivity, so there should
be no need for manual adjustment. If manual adjustment is desired, refer to
Time Delay settings in DIP Switch legend.
Reset sensor Time Delay to factory settings by moving DIP Switches 1 and
2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out
of its current position, wait 3 seconds, and then back to its original position).
Override
The override setting allows the sensor to operate as a service switch in the unlikely event of failure.
1. Move DIP Switch 8 up.
2. The Pushbutton can be used to manually turn lights ON or OFF.
Warranties and Limitation of Liability
DIP Switch Settings
Troubleshooting
Please refer to www.coopercontrol.com under the Legal section for our terms and conditions.
Checkout and Adjustment
120/277 VAC
BLACK
BLUE
NEUTRAL
GROUND
GREEN
LOAD 1
LOAD 2
LOAD 1
BLACK
BLUE
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTEDMOTION LAST TIMES-OUT.
GROUND
GREEN
120/277 VAC
BLACK
BLUE
GROUND
GREEN
TRAVELER
WIRES
Wiring Diagram 3:
120/277 VAC single level single circuit three-way wiring diagram
Wiring Diagram 2:
120/277 VAC single level switch dual level wiring using a toggle switch wiring diagram
5 Minutes
Auto*
*Self-Adjusts to
10 min. user mode
Time Delay
DIP Switch
Activation
PIR Sensitivity
Override
Relay 1
Not Used
EcoMeter
Walk-Through Mode
Default =
30 Minutes
15 Minutes
1
2
DIP Switch Legend
6
Disable
Enable
4
3
Auto
Manual
5
Full
50%
8
7
Enable
Disable
Disable
Enable
1 2 3 4 5 6 7 8
Adjustments should be made with the HVAC system on so that the installer will be able to detect the effect of airflow on
the operation of the ONW-P-1001-MV. Use only insulated tools to make adjustments.
Immediately after applying power to the lighting circuit, wait approximately two minutes for the switch to power up
and stabilize.
Self-Adjust
Sensor is shipped in self-adjust mode. This applies to Time Delay and PIR sensitivity. In preparation for the Installer Test,
the Time Delay is set to 15 seconds, after the sensor is installed, powered ON and has stabilized, the unit will Time-out 15
seconds after the last motion detected. Coverage and sensitivity can be confirmed by watching the Red (PIR) indicator LED
on the front of the sensor, while moving around the room.
1. Walk around the room and monitor LEDs.
2. Stand in different parts of the room and wave your hands.
LED should only turn ON for one second with each motion.
(If LED does not turn ON, go to Installer Adjustments –
Sensitivity Adjustment Section)
3. Stand still three to four feet away from sensor for five
seconds. LED should not turn ON. (If LED turns ON, go to
Installer Adjustments – Sensitivity Adjustments section)
4. Walk outside the room and wait 15 seconds for the lights
to turn OFF. (If lights do not turn OFF go to Installer
Adjustments Section)
5. Re-enter the room to activate sensor. (If lights do not turn
ON go to Troubleshooting Section)
6. At this point you can reattach the pushbutton and exit
the room. When the sensor times-out and is OFF for five
minutes, the unit will go to a 10 minute Time Delay user
mode setting.
Note:
To place i nto Test Mode, toggle DIP Switch 8 out of its current position, wait 3 seconds, and then back into its original position.
ON/OFF Button
PIR Lens
DIP Switches
Daylight
Sensor Level
Adjustment
Red (PIR)
Detection LEDs
1 2
3 4 5 6
7 8
DIP Switches
1 & 2
Issue
Possible Causes
Suggestions
Lights
Will Not
Turn ON
automatically
Sensor is in Manual ON mode
Press Pushbutton. If Auto Mode
is desired change Activation Mode to Auto.
Sensor was turned OFF manually. If the Sensor
was turned OFF manually before the Time Delay
expired, lights will remain OFF for the remainder
of the Time Delay.
Check EcoMeter LED. If LED is ON this is
an indication that the lights were turned OFF manually.
Press the Pushbutton to turn the lights back ON.
Daylight Feature Enabled
If all lights are required to turn ON
adjust daylight potentiometer.
Power interruption
Check incoming voltage and/or wiring.
Lights
Will Not
Turn ON
manually
Daylight Feature Enabled
If all lights are required to turn ON
adjust daylight potentiometer.
Power interruption
Check incoming voltage and/or wiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override
Make sure sensor is not in Override Mode (DIP Switch 8 up).
Self-Adjust
If sensor is in Self-Adjust Mode, it may be possible for the
unit to have increased the Time Delay to a 30 minute delay.
If the lights do not turn OFF after 30 minutes follow next step.
30 Minute Delay
Maximum Time Delay is 30 Minutes. Check DIP Switches
to verify DIP Switch settings. If lights do not turn OFF at the
set Time Delay, check next step.
PIR activated by heat source other than occupant
Move DIP Switch 5 up.
Lights
Will Not
Turn OFF
manually
Call Technical Services
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only
one circuit per relay. Both circuits must be fed from the same phase.
Installer Adjustments