Operation procedure :
SET
Press
before Power ON
Operation level
Power ON
Press
SET
for 3 sec
Parameter setting
PV
Press
>
Press
SET
Press
>
Press
>
Press
>
Press
>
Input High
Input Low
Decimal
Press
SET
Press
SET
Press
SET
Decide the decimal point
position for the PV Display
Set the Scaling Low using keys
>
>
Set the Input High using keys in %
>
>
Set the input High value 100 for 0-20 mA
Set the input Low value 0 for 0-20 mA
Set the Input Low using keys in %
>
>
Decimal Setting
Scaling High
Scaling Low
Set the input Low value 20 for 4-20 mA
Set the input Low value 0 for 0-10 V
Set the input High value 100 for 4-20 mA
Set the input High value 100 for 0-10 V
Press
SET
Set the Scaling High using keys
>
>
Press
>
Press
>
Press
>
Very High
High
Low
Very Low
Press
>
Press
>
Press
>
Press
SET
Press
SET
Press
SET
Press
SET
Set the Very Low alarm value using
keys in Scaled value
>
>
Set the Low alarm value using
keys in Scaled value
>
>
Set the High alarm value using
keys in Scaled value
>
>
Set the Very High alarm value using
keys in Scaled value
>
>
If PV is greater than
then
V HIGH ALM
Will ON
Very High
If PV is greater than
and less
than
Very High
then
HIGH ALM
Will ON
High
If PV is less than
and greater
than
Very Low
then
LOW ALM
Will ON
Low
If PV is less than
then
V LOW ALM
Will ON
Very Low
If PV is less than
High
and greater
than
Low
then
PASS ALM
Will ON
Initial Setting
Scaling Low Value
Scaling High value
Press
>