Vacuum pump

INSTALLER

Humid air left inside the refrigerant circuit can cause com-

pressor  malfunction. After  having  connected  the  indoor 

and  outdoor  units,  bleed  the  air  and  humidity  from  the 

refrigerant circuit using a vacuum pump.

(1) Unscrew and remove the caps from the 2-way and 3-

way valves.

(2) Unscrew and remove the cap from the service valve.

(3) Connect the vacuum pump hose to the service valve. 

(4) Operate the vacuum pump for 10-15 minutes until an 

absolute vacuum of 10 mm Hg has been reached.

(5) With  the  vacuum  pump  still  in  operation,  close  the 

low-pressure knob on the vacuum pump coupling. Stop 

the vacuum pump.

(6) Open  the  2-way  valve  by  1/4  turn  and  then  close  it 

after  10  seconds. Check  all the  joints for  leaks  using 

liquid soap or an electronic leak device.

(7) Turn the body of the 2-way and 3-way valves. Discon-

nect the vacuum pump hose.

(8) Replace and tighten all the caps on the valves.

BLEEDING

INSTALLER

INDOOR

UNIT

Vacuum pump

 

Vacuum pump

Connect to the

indoor unit

Location

Twisting moment (N.m)

35-40
60-65

45-50
70-75

Φ1

2

Φ1

9

Diameter (mm)

Φ9

.52

Φ1

6

15-20

Φ6

(9) If the specification of outdoor unit gas valve is 3/8

     but curstomer needs to install 1/2

indoor unit so that 

     it is need to use a “pipe joint subassembly” (Code 06643008) 

     to make a conversion joint with outdoor unit gas valve and 

     connection pipe, as show in following.

conversion joint

Refrigerant fluid direction of flow

3-way valve

2-way valve

Service 

inlet

(2) Turn

(8) Secure

(7) Turn to open fully

(2) Turn

(8) Secure

Valve cap

(6) Open by 1/4 turn

(7) Turn to open fully

(2) Turn

(8) Secure

Valve cap

8

Drain-water hole

Bottom frame

Drain plug

Hose (available commercially,
inner dia. 16mm)

Drain connecter

Use bolts to secure the unit to a flat, solid floor.

When mounting the unit on a wall or the roof, make

sure the support is firmly secured so that it cannot

move in the event of intense vibrations or a strong

wind.

Do not install the outdoor unit in pits or air vents

Installing the pipes

Install the drain fitting and the drain hose(for

model with heat pump only)

Condensation is produced and flows from the outdoor unit 

when the appliance is operating in the heating mode. In order

not to disturb neighbours and to respect the environment,

install a drain fitting and a drain hose to channel the conden-

sate water. Install the drain fitting and rubber washer on the 

outdoor unit chassis and connect a drain hose to it as shown 

in the figure.

Use suitable connecting pipes and equipment for the 

refrigerant R410A.

Wrap all the  refrigerant pipes and joints.
Tighten the connections using two wrenches working 

in opposite directions.

Caution: Installation Must be Performed in Accordance

with the NEC/CEC by Authorized Personnel Only

Models(m)

18K

24/30K

Max. connection pipe length

20

70

Max. connection pipe length(Simple

one indoor unit)

10

20

The refrigerant pipes must not exceed the maximum 

heights 5m(18K) or 

10m(24K&30K).

INSTALLING THE OUTDOOR UNIT

Summary of Contents for WHD(18)ND3CO

Page 1: ...ers Thank you for choosing Residential Air Conditioners please read this owner s manual carefully before operation and retain it for future reference Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com GREE ELECTRIC APPLIANCES INC OF ZHUHAI 66163066 ...

Page 2: ...N GENERA L INFORMATION Please read this owner s manual carefully before operating the unit and keep it carefully for consultation The products in this manual may be different with the real one according to different models some models have displayer and some models without displayer the position and shape of the displayer please refer to the real one The air conditioner you have purchased is in co...

Page 3: ... will lead to an electric shock or fire so you should contact the service center to repair Earthing The unit must be reliably earthed The earthing cable shall be connected to the special earthing device in the construction Never cut off or damage power cables and control wires If the power cable and signal control wire were damaged change them by professional When cleaning it is necessary to stop ...

Page 4: ...ed by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard OUTDOOR UNIT No Description 1 Air outlet grille 2 Valve 1 2 3 GENERAL INFORMATION The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube Note the above figures are only intended to a simple diagram of the appliance and may not correspon...

Page 5: ...ction 40 40 4 0 g mm mm mm mm mm L P H A B 4 0 Fuse or air switch 2200 2200 890 362 700 560 368 MODE GWHD 24 ND3CO GWHD 18 ND3CO 208 230V 1 60Hz mm2 Refrigerant gas R410A GWHD 30 ND3CO Minimum power cable section 25 2 5 g mm mm mm mm mm L P H A B Fuse or air switch 1350 818 378 596 550 354 MODE Electricity supply Electrical data Electrical data Electricity supply 208 230V 1 60Hz mm2 Refrigerant ga...

Page 6: ...L CONNECTIONS INSTALLER the unit A and unit B must be corresponding to each other respective national wiring regulations To the power supply To unit B cable cable To unit A 5 GWHD 18 ND3CO GWHD 18 ND3CO L1 L2 L1 L1 L2 L2 ELECTRICAL CONNECTIONS INSTALLER cable cable cable 5 power cable and power cable with the terminal at the row of connection and fix the connection The fitting line distributing mu...

Page 7: ...esponding to each other respective The appliance shall be installed in accordance with national wiring regulations Do not install the outdoor unit where it is exposed to the sunlight Note the above figures are only intended to be a simple e h t o t d n o p s e r r o c t o n y a m d n a e c n a i l p p a e h t f o m a r g a i d appearance of the units that have been purchased To the power supply To...

Page 8: ...r connection cable cover 2 If connecting with two indoor units the connection cable should be put in from hole A and hole B 3 If connecting with three indoor units the connection cable should be put in from hole A B and C 4 If connecting with four indoor units the connection cable should be put in from hole A B C and D All power cables and connection cables must be protected with conduits To the p...

Page 9: ... Refrigerant fluid direction of flow 3 way valve 2 way valve Service inlet 2 Turn 8 Secure 7 Turn to open fully 2 Turn 8 Secure Valve cap 6 Open by 1 4 turn 7 Turn to open fully 2 Turn 8 Secure Valve cap 8 Drain water hole Bottom frame Drain plug Hose available commercially inner dia 16mm Drain connecter Use bolts to secure the unit to a flat solid floor When mounting the unit on a wall or the roo...

Page 10: ...HD 18 ND3CO GWHD 24 ND3CO GWHD 30 ND3CO 30cm Air inlet side or above 50cm or above Space to the wall 200cm Air outlet side or above 30cm Space to the cover or above or more Space to the cover 50cm INSTALLER Use suitable instruments for the refrigerant R410A Do not use any other refrigerant than R410A Do not use mineral oils to clean the unit Contact service center before installation to avoid the ...

Page 11: ...ecified on the nameplate The unit may bread down or the components may be burned out Are the lines and pipelines correctly installed The unit may bread down or the components may be burned out Has the unit been safely grounded Risk of electrical leakage Are the models of lines in conformity with requirements The unit may bread down or the components may be burned out Are there any obstacles near t...

Reviews: