3
Test Operation & Troubleshooting & Maintenance
50
Desynchronizing
Desynchronize
Pc
51
Compressor stalling
Comp. stalling
H7
52
Communication error
drive-main com.
LE
53
Radiator or IPM or PFC module overtemperature
Overtemp.-mod.
P8
54
Radiator or IPM or PFC module temperature sensor error
T-mod. sensor
P7
55
Charging circuit error
Charge circuit
Pu
56
Incorrect AC voltage input
AC voltage
PP
57
Drive board temperature sensor error
Temp-driver
PF
58
AC contactor protection or input zero crossing error
AC contactor
P9
59
Temperature drift protection
Temp. drift
PE
60
Current sensor connection protection (current sensor not connected to
phase U/V)
Sensor con.
PD
61
Communication error to the outdoor unit
ODU Com.
E6
62
Communication error to the indoor unit
IDU Com.
E6
63
Communication error to the drive
Driver Com.
E6
64
Solar kit-superheating
Solarsuperheat
F6
3 Flow Chart Of Troubleshooting
3�1 Comp High-pressure Protection E1
Comp High-pressure protection E1
Check if the High-pressure switch
is broken
Replace the High-pressure
switch
Check if the High-pressure switch
wiring is loose.
Replace the wiring
Check if the water in
the tank is enough
Check if the installation of
tank temp sensor is correct
Check if the gas valve and
liquid valve are fully open
Check if the electric expansion
valve can work normally
Fill the tank with the water
Install rightly the
tank temp sensor
Fully open the valve
Replace the electronic
expansion valve
yes
no
yes
no
no
no
yes
yes
yes
yes
no