DIAGNOSTIC CODES
No.
1
2
3
4
5
6
7
8
Description
If outdoor unit detects the high pressure switch is cut off for 3-sec
successively, high pressure protection will occur. All the loads
(except the 4-way valve in heating mode) will be switched off.
In this case, all the buttons and remote control signals except
ON/OFF button will be disabled and system won't be recovered
automatically. Switch off the unit or re-energize the unit after
cutting off power to eliminate this protection.
If indoor unit detects the evaporator temperature is lower than
protective temperate value after the unit has been running for a
period of time under cooling or dry mode, the unit will report this fault,
in which case the compressor and outdoor fan motor will be stopped.
The unit will not run until evaporator temperature is higher than
the protective temp. value and the compressor is stopped for 3-min.
If outdoor unit detects the discharge temperature is higher than
protective temperature value, the unit will report high discharge
temperature protection. If the protection occurs over 6 times, the
unit cannot be recovered automatically. Switch off the unit or
re-energize the unit after cutting off power to reset this protection.
If the outdoor unit does not receive data from indoor unit,
communication malfunction will be reported. If there is
communication abnormality between display board and indoor
unit, communication malfunction will be reported.
If the indoor unit does not receive signal from indoor fan motor
for 30-sec successively when the fan motor is operating, indoor
fan motor malfunction will be reported. In this case, the unit can
automatically resume operation after stopping. If the malfunction
occurs 6 times within one hour, the unit cannot be recovered
automatically. Switch off the unit or re-energize the unit after
cutting off power to eliminate this malfunction.
If indoor unit detects the condensate overflow switch warning for
8-sec successively, the system will enter condensate overflow
protection. The unit will shut off and will not recover automatically.
Switch unit off and then switch it on to eliminate this malfunction.
If indoor unit detects the indoor ambient temperature sensor is open
circuit or short circuit for 5-sec successively, indoor ambient temp.
sensor malfunction will be reported. The unit can automatically
resume operation after the malfunction disappears. If indoor ambient
temperature sensor malfunction occurs in fan mode, only the error
code is displayed and the indoor unit will operate normally.
If indoor unit detects the evaporator temperature sensor is open
circuit or short circuit for 5-sec successively, evaporator temperature
sensor malfunction will be reported. The unit can automatically
resume operation after the malfunction disappears. If evaporator
temperature sensor malfunction occurs in fan mode, only the error
code is displayed and the indoor unit will operate normally.
Error
Code
E1
E2
E4
E6
E8
E9
F0
F1
Malfunction
Name
High Pressure
Protection
Indoor Coil
Freeze
Protection
Compressor
High Discharge
Temperature
Protection
Communication
Malfunction
Low Indoor
Airflow
Condensate
Overflow
Protection
Indoor Ambient
Temperature
Sensor at
Return Air Inlet
Malfunction
Indoor
Evaporator Coil
Temperature
Sensor
Malfunction
Origin of
Malfunction
High Pressure
Switch
Indoor
Evaporator
Temperature
Sensor
Compressor
Discharge
Temperature
Comm. Failure
Between Indoor
and Outdoor
Main Board
Indoor
Fan Motor
Overflow
Switch
Indoor
Ambient
Temperature
Sensor
Evaporator
Coil
Temperature
Sensor
Error Codes
The U-Match System has on board diagnostics. The indoor unit and Tether Controller will display
error codes. The following is a summary of the codes with explanation: