52
for North America
Ultra Heating GMV5 Multi VRF
ODU
IDU
Indoor
No.
Indoor
①
Indoor
②
Indoor
③
Indoor
④
Model
Duct type
GMV-ND18PLS/A-T(U)
Duct type
GMV-ND12PLS/A-T(U)
Duct type
GMV-ND09PLS/A-T(U)
Duct type
GMV-ND09PLS/A-T(U)
Liquid pipe:
No.
A
B
C
D
Pipe size
Φ9.52mm(3/8inch)
Φ9.52 mm(3/8inch)
Φ9.52 mm(3/8inch)
Φ6.35 mm(1/4inch)
Length
10m(32-3/4feet)
5m(16-3/8feet)
5m(16-3/8feet)
5m(16-3/8feet)
No.
a
b
c
d
Pipe size
Φ9.52mm(3/8inch)
Φ6.35 mm(1/4inch)
Φ6.35 mm(1/4inch)
Φ6.35 mm(1/4inch)
Length
3m(9-3/4feet)
3m(9-3/4feet)
2m(6-5/8feet)
1m(3-1/4feet)
T
otal length of each liquid pipe
Φ
9.52:
A+B+C+a=10+5+5+3=23m(75-1/2
feet)
Φ
6.35: D+b+c+d=5+3+2+1=
1
1m(36feet)
NOTICE!
Liquid pipe that is within 20m(65-5/8feet)doesn’t need to be added with refrigerant.
Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+
1
1×0.022 = 0.404kg(14oz).
8 Installation of Condensate Pipes
8.1 Ensure an inclination degree of more than 1% when connecting the drain pipe to the IDU.
1000~1500
(mm)
Inclination degree
of more than
1/100
Correct connection
Incorrect connection
facilitate further maintenance.
When connecting the drain pipe branches to the main pipe, lead through from the above part of the main pipe.
If the
air
volume
of the
IDUs is
high
and outdoor air resorption
may
be caused by
negative
suction
pressure,
provide
a u-type drain trap
Summary of Contents for ULTRA heating GMV-36WL/B-T
Page 1: ...Ultra Heating GMV5 Multi VRF for North America R410A GC201603 1 ...
Page 3: ...1 Ultra Heating GMV5 Multi VRF for North America PRODUCT PRODUCT ...
Page 15: ...13 for North America CONTROL CONTROL Ultra Heating GMV5 Multi VRF ...
Page 38: ...36 Ultra Heating GMV5 Multi VRF for North America INSTALLATION ...
Page 66: ...64 for North America MAINTENANCE Ultra Heating GMV5 Multi VRF ...
Page 71: ...69 for North America Ultra Heating GMV5 Multi VRF 3 Discharge temperature protection ...
Page 95: ...JF00302969 ...