U-Match Series Duct Type Unit
29
The vertical height of the drain hose should be 75mm or less so that it is
unnecessary for the drain port to withstand additional force.
When multiple drain hoses are used, their installation should be performed as
shown in the figure below.
NOTICE:
The specification of the selected merged drainage pipe shall be appropriate for
the operation capacity of the unit.
(1) Drain branch should be connected to the vertical or horizontal part of the main
drain pipe.
(2) Horizontal pipe should not be connected to the vertical pipe that is on the same
level. It should be connected in the following way:
1) Attach the 3-way connection of the drainage pipe joint.
2) Attach the drain elbow.
3) Attach the horizontal pipe.