Troubleshooting Outdoor Components
The exhaust temperature sensor monitors the refrigerant discharge temperature and will send information to the
inverter control board for system operation.
The following actions can occur:
Exhaust Temperature > 208 F - Compressor will not rise above present level
Exhaust Temperature > 217 F - Compressor will run at reduced frequency
Exhaust Temperature < 194 F - Compressor off for 3 minutes minimum, the compressor will restart
Error Code F5 will be generated if the sensor is open or shorted. Please refer to the troubleshooting section for
more detailed information.