23
GMV5 HR HEAT RECOVERY
VRF Units Technical Sales Guide
Outdoor Units_Heat Recovery
Ton
18
20
22
Model
-
GMV-Q216WM/B-U(U)
GMV-Q240WM/B-U(U)
GMV-Q264WM/B-U(U)
Module combination
-
GMV-Q96WM/B-U(U)+
GMV-Q120WM/B-U(U)
GMV-Q120WM/B-U(U)+
GMV-Q120WM/B-U(U)
GMV-Q72WM/B-U(U)+
GMV-Q96WM/B-U(U)+
GMV-Q96WM/B-U(U)
Pipe
Connection
Low pressure Gas
Pipe Size
mm
28.6
34.9
34.9
in.
1 1/8
1 3/8
1 3/8
high pressure gas
pipe
mm
28.6
28.6
28.6
in.
1 1/8
1 1/8
1 1/8
Liquid Pipe Size
mm
15.9
15.9
19.05
in.
5/8
5/8
3/4
Dimensions
(width×
depth× height)
External Dimension
mm
1340×765×1605
+1340×765×1605
1340×765×1605
+1340×765×1605
1340×765×1605
+1340×765×1605
+1340×765×1605
in.
52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
Packaging
Dimension
mm
1420×840×1775
+1420×840×1775
1420×840×1775
+1420×840×1775
1420×840×1775
+1420×840×1775
+1420×840×1775
in.
55-7/8×33-1/8×69-
7/8+55-7/8×33-1/8×69-
7/8
55-7/8×33-1/8×69-
7/8+55-7/8×33-1/8×69-
7/8
55-7/8×33-1/8×69-
7/8+55-7/8×33-1/8×69-
7/8+55-7/8×33-1/8×69-
7/8
Weight
Net Weight
kg
315+370
370+370
305+315+315
lbs.
694+816
816+816
672+694+694
Gross Weight
kg
330+385
385+385
320+330+330
lbs.
728+849
849+849
705+728+728
Maximum qty of connected indoor
units
unit
36
39
46
Protection
Devices
High Pressure
Protection
High pressure sensor, High pressure switch
Compressor /Fan
Over-current protection, Over-heat protection
Inverter
Over-current protection, Over-heat protection, High/Low voltage protection,
Remark
① .
It refers to the operation power of compressor under ARI test conditions (Condensing temp. 130
℉
;
Evaporating temp.45
℉
; Return gas temp.65
℉
; Liquid temp.115
℉
) at 60Hz.
② .
Oil charge includes the total oil amount of outdoor units, residual oil amount of compressor and oil separate
tank. When replacing the compressor or oil separate tank, only the corresponding required oil amount shall
be charged.