Super Free Match Series
27
Indoor unit 6 is connected
Flash 10 times
Indoor unit 7 is connected
Flash 11 times
Indoor unit 8 is connected
Flash 12 times
Indoor unit 9 is connected
Flash 13 times
Indoor unit anti-freeze protection
E2 E2
Indoor temperature sensor error
F1 F1
Indoor evaporator midway
temperature sensor error
F2 F2
Temperature sensor error for liquid
pipe of BU module
b5 b5
Temperature sensor error for gas pipe
of BU module
b7 b7
Running mode conflicts
E7 E7
Communication error
E6
E6
indoor
unit address
Communication error between the
main board and driving board
P6
Communication error between the
main board and testing board
CE
Gas sensor error of indoor unit
Fn
Humidity sensor error of indoor unit
L1
Water full error of indoor unit
E9 E9
Jumper terminal error of indoor unit
C5 C5
Phase lack of power supply
dJ
Fan motor error of outdoor unit
L3
Refrigerant recovery mode
Fo Fo
Display mode of Red LED and Yellow LED: At intervals of half a second, flash for half a
second; if there are several malfunctions, it will display the error codes by turns
at intervals of
one second.
Display mode of Green LED: At intervals of 1/4 second, flash for 1/4 second; and it displays
the running states by turns
at intervals of half a second.