27
EXTENDED PERFORMANCE RATINGS
25°F
22,145 16,443 23,936 17,330 25,587 18,422
35°F
21,641 16,423 23,047 16,825 24,167 17,473
45°F
20,572 15,799 22,000 16,324 23,571 17,089
55°F
19,805 15,329 21,119 15,839 22,640 16,528
65°F
19,130 14,864 21,049 15,977 22,320 16,316
75°F
18,378 14,371 19,800 15,226 21,296 15,716
85°F
17,640 14,006 18,900 14,591 20,520 15,329
95°F
16,740 13,375 18,000 14,382 19,692 14,789
105°F
15,840 12,862 17,060 13,614 18,540 14,239
115°F
14,939 12,309 15,839 12,829 16,919 13,248
5°F
15,608 15,608 14,731 14,731 14,370 14,370
15°F
16,684 16,684 15,221 15,221 15,130 15,130
25°F
17,702 17,702 16,802 16,802 15,846 15,846
35°F
18,691 18,691 17,300 17,300 16,574 16,574
45°F
19,667 19,667 19,000 19,000 17,849 17,849
55°F
19,693 19,693 19,124 19,124 18,287 18,287
65°F
19,600 19,600 19,314 19,314 18,719 18,719
OUTDOOR AMBIENT
TEMPERATURE (DB)
OUTDOOR AMBIENT
TEMPERATURE (DB)
(80% RH)
INDOOR ENTERING AIR TEMPERATURES (DB) 50% RH
INDOOR ENTERING AIR TEMPERATURES (DB)
62°F
TC SHC
65°F
TC SHC
67 F
TC SHC
70°F
TC SHC
72 F
TC SHC
75°F
TC SHC
Model No: MULT18HP230V1A
18,000 BtuH
Cooling Performance
Heating Performance
TC- Total Capacity (BtuH) SHC- Sensible Capacity (BtuH)
Capacity data is based on the following conditions:
Cooling Nominal Test Conditions
Heating Normal Test Conditions
Indoor: 80°F DB/67°F WB
Indoor: 70°F DB/60°F WB
Outdoor: 95°F DB/75°F WB
Outdoor: 47°F DB/43°F W
OUTDOOR AMBIENT
TEMPERATURE (DB)
INDOOR ENTERING AIR TEMPERATURES (DB) 50% RH
62°F
TC SHC
67°F
TC SHC
72°F
TC SHC