5
1.2.3.4
Product size
1.2.3.5
Installation and usage notices for photoelectric isolation converter
WARNING! It must be installed inside the room, avoid collision, exposure or rain. It’s suggested to be placed with the
computer inside the monitor room.
WARNING! The original equipment must be used, alternative products of the other models or brands are not allowed.
WARNING! Separate power supply is required, AC socket of 220V must be installed to supply power.
1.2.4
Introduction of photoelectric isolation repeater
1.2.4.1
Function introduction
The function of photoelectric isolation repeater:
1
)
Ensure signal completeness when the node distance of the whole communication network exceeds 800M to prevent signal
reduction in long-distance communication.
2
)
At present, general photoelectric isolation repeater can support the communication signal completeness for 32 nodes.
When the number of communication node in network exceeds 32, the communication signal will not be complete. To ensure
reliable signal transmission, we require that when the number of node in network exceeds 30, repeater must be adopted to transit
signal to ensure the completeness of communication signal.
Modbus Gateway(Mini)