D Series Modular Air-cooled Scroll Chillers
14
Blind plug
NOTE
•
Keep the purge valve of the water system open in order to drain the evaporator and condenser
completely.
Diameters of Entering/Leaving Water Pipes
Diamter
(mm)
Cooling load
(kW)
DN15
0~3
DN20
3~7
DN25
5~13
DN32
10~25
DN40
15~38
DN50
29~75
DN65
46~126
DN80
84~230
DN100
167~461
DN125
314~586
DN150
523~1151
DN200
1068~2094