EnviroAir High Wall Ductless Split Systems
6
Remove indoor and outdoor units
from
the carton/box. Indoor unit carton con-
tains, remote control and batteries, en-
sure these are kept in a safe place during
installation.
6” from ceiling minimum
CEILING
WALL
WALL
8”
from wall
minimum
8”
from wall
minimum
4ft from fl oor (minimum)
6ft plus from fl oor (optimum)
FLOOR
ENVIROAIR HIGH WALL DUCTLESS SPLIT SYSTEMS
INDOOR UNIT INSTALLATION
Follow Instructions, failure to follow
instructions may cause possible mal-
function and void any warranty.
!
!
CAUTION
Locate area to install indoor unit
the
unit should be located a minimum of 6 ft.
from the fl oor and 6” from the ceiling.
Choose an area where the wall is plumb
and determine how to best to run the unit
interconnects.
Ensure no obstacles to airfl ow are directly
in front of the unit, for a minimum of 12 ft
for 9,000/12,000 Btuh units and 16 ft for
18,000/24,000 Btuh units.
Do not install the Indoor unit units in areas
exposed to high humidity
(Relative Hu-
midity of 80% or more)
, direct sunlight and
direct heat from stoves or other devices.