GREE Air-ccoled Closed Control Unit Service Manual
47
“
Auto/Manual
”: When “manual” is displayed, the module is in the manual operation state.
By touching it, the state will switch to auto running. But the reverse setting should be set in the
“
Parameter Setting
→
Manual Debugging
.” In addition, if “entire” is set, manual mode is
shielded.(Default to auto)
“
Duty Time
”: It means the alternately continuous running time of the entire running state of
modules and the setting time range is 1~720 hours. Default time range is 96 hours. When the
accumulated running time of the module has been reached the preset time for alternate running,
the module will stop and the other standby module will start in order to make each module run in
turn.
“
Standby Units
”: It means the standby units of modules stopped. Only the modules which
are set to states of Link, ON, Entire running would be set to standby. When the Qty is 0, there
are no functions of alternation and standby; when the standby units are bigger or equal to the
Qty of entire running module units, all units that are qualified to be standby units will stop to be
standby and there is no alternative running unit.
(
3
)
Time & Date Setting Interface
Slightly press the button “Time Setting” to enter the interface of “Time & Date Setting”.
It can be revised by touching the corresponding numeric box.
(
4
)
Timer ON/OFF Setting
Slightly press the button “Timer Setting” to enter the interface of “Timer On/Off Setting”.
This function won’t be effective if module is in entire control or manual state, but will be valid
when module is in independent auto mode.