MODULAR MINI CHILLER MAINTENANCE
40
5. Phase Inversion (missing) Protection(Power Off)
Yes
Yes
Yes
No
No
Yes
No
No
Yes
Check if it happens
frequently. If necessary,
replace mainboard
Misdeclaring alarm
of controller
Contact with supplier
Replace inverse
protector
Inverse protector
is broken
Check power supply
Phase missing
Adjust connection
wires
Phase sequence of
power supply is
wrong
Phase
inversion(missing)
protection