Unit Installation

Notes:

① 

The two-way valve is very important to prevent dew condensation on the floor and radiator while cooling 

mode;

② 

Type of thermostat and specification should be complied with installation of this manual;

③ 

The by-pass valve must be installed to secure enough water flow rate, and should be installed at the 

collector.

CASE 2: Connection between the Electric Heater and the Main Unit

Two groups of electric heaters are available, as well as control terminals for two groups of auxiliary electric 

heaters. These two groups of electric heaters can be activated at the same time. When only one group of the 
electric heater is installed, please follow the wiring of any group of the diagram shown below.

(1) See the following statement for installation of two groups of auxiliary electric heaters, including wiring of 
the AC contactor, the thermostat and the tank-type electric heater.

  

Wiring of the AC Contactor

L1, L2 and L3 are three-phase input terminals. T1, T2 and T3 are three-phase output terminals. A1 and A2 

are terminals of input and output signals which are used to control the AC contactors. NO and NC are normally 
open and closed terminals of the AC contactors.

The tank-type electric heater and AC contacts should be selected according to the selection instructions 

and the thermostat and its upper limit should be decided by the protection function of the electric heater.

In order to ensure product quality and service life, it is unallowable to do wiring directly at the main board 

by the user themselves to prevent the main board from being damaged. The AC contactor control signal input 
terminal X17 (AC contactor 1) and X18 (AC contactor 2) of the main board AP1 should be connected to terminal 
7 and terminal 8 of the electric box. The single pins of terminal CN26 (AC contactor 1) and CN27 (AC contactor 2) 
should be connected to terminal 35 and 36 of the electric box. Besides, other two pins of CN 26 and CN27 both 
should be connected to XT2 (see the diagram below for more details).

Only qualified cables are allowed and see the table below for the corresponding wiring terminals.

No.

 Wiring Terminal

AC Contactor 1

7—A1

35—2T1

AC Contactor 2

8—A1

36—2T2

  

Wiring of the Thermostat

The proper limit of the thermostat should be selected based on the protection function of the electric heater.
Firstly, short-circuit the ON/OFF control signal output terminals of AC contactor 1 and AC contactor 2, and 

then connect them with the thermostat in series. Do not let the temperature of the external wall of the tank-type 
electric heater too high (see the diagram below for more details). After that, apply heat-conducting paste on the 
sensing probe and then insert it to the sensing hole to sense the temperature of the external wall of the tank-
type electric heater.

  

Wiring of the Tank-type Electric Tank

The tank-type electric heater with proper power output should be used and the heating pipe should be 

installed at the water inlet side of the unit.

Three-phase wiring for the electric heater should be supplied by the user themselves. A new electric box is 

recommended to be used. See the diagram below for more details.

When protection function of the thermostat is required, the sensing probe applied with heat-conducting 

paste should be inserted into the sensing hole after wiring of the electric heater has been finished.

Summary of Contents for HLR10Pd/Na-K

Page 1: ...Change for life GREE ELECTRIC APPLIANCES INC OF ZHUHAI Mini Chiller Unit Installation eries...

Page 2: ...cation 6 4 4 Outline Dimension of the Mini Chiller 7 4 5 Installation Clearance Data 8 4 6 Electric Wiring 8 4 7 Wiring of the Terminal Board 9 4 8 Wiring of the 2 Way Valve 10 4 9 Wired Controller 11...

Page 3: ...kitchen or the plastic would be aged broken off or the polluted evaporator would lead to water leak and poor performance Do not place the unit where there is corrosive gas like sulfur dioxide or the...

Page 4: ...cording to installation manual 3 Do not connect to power until all installation work is completed 2 Filed Supplied Pipes and Valves Name Picture Usage Water Filter It is used to remove foreign matters...

Page 5: ...nstallation Examples CASE 1 Connection of Terminals for Heating and Cooling Under floor Loop Fan Coil Unit and Radiator B M Under Floor Coil FCU 1 T Radiator B T Bypass valve field supplied High tempe...

Page 6: ...maged The AC contactor control signal input terminal X17 AC contactor 1 and X18 AC contactor 2 of the main board AP1 should be connected to terminal 7 and terminal 8 of the electric box The single pin...

Page 7: ...Installation Diagramof the Electric Heater with the thermostat 2 See the following statement for installation of two groups of auxiliary electric heaters including wiring of the AC contactors and the...

Page 8: ...eet actual demands should be avoided Never open the electric box for wiring of the mainboard by the user themselves 4 2 Pre Installation 1 Installation of the unit must be in accordance with national...

Page 9: ...7 Unit Installation 4 4 Outline Dimension of the Mini Chiller HLR8Pd Na K HLR10Pd Na K 1390 412 361 388 890 HLR12Pd Na M HLR14Pd Na M 367 340 1390 1430...

Page 10: ...ng and moving must be 40 below to prevent center of the unit from moving 2 The monobloc unit should be installed on concrete base that is 10cm height 3 Requirements on installation space dimension of...

Page 11: ...9 Unit Installation HLR12Pd Na M HLR14Pd Na M 4 7 Wiring of the Terminal Board HLR8Pd Na K HLR10Pd Na K...

Page 12: ...ow Yes NC 2 wire 230V 50Hz 1Ph AC Closing water flow Yes Opening water flow Yes 1 Normal Open type When electric power is NOT supplied the valve is open When electric power is supplied the valve is cl...

Page 13: ...ram At the field installation it should be wired at the terminal board of the 2 way valve 1 4 9 Wired Controller Wired controller wiring guidance 4 10 Wiring of Other Auxiliary Heat Sources Other auxi...

Page 14: ...loor is approximately 1 5 meters Remote air temperature sensor can not be located where the area may be hidden when door is open Remote air temperature sensor can not be located where external thermal...

Page 15: ...e product For other constrains please refer to previous pages about the remote air temperature sensor Do not connect external electric loads Wire 220V AC 24V AC and 220V GND 24V GND should be used onl...

Page 16: ...g pipe proper 8 Are the nilometer of water tank water temperature indicator controller manometer pressure relief valve and automatic discharge valve etc installed and operated properly 9 Does power su...

Page 17: ...ce firstly Recheck the phase sequence before start up to avoid reverse rotation of the compressor which may damage the unit 4 Apply the universal electric meter to measure the insulation resistance be...

Page 18: ......

Reviews: