Unit Installation

21

22

23

24

25

26

Thermostat

XT3

220V AC

24V AC

2220V GN

D

224V GN

D

OFF

OFF

HEAT

COOL

COOL

HEAT

27

28

29

30

Thermostat

How to Wire Thermostat 

(1) Uncover the front cover of the monobloc unit and open the control box.
(2) Identify the power specification of the thermostat, if it is 230V , find terminal block XT3 as NO.21~25; 

Otherwise, if it is 24V, find terminal block XT3 as NO.26~30; 

(3) 

If it is the heating/cooling thermostat, please connect wire as per the figure above;

CAUTION!

① 

Never use 230V AC and 24V AC thermostat at the same time, otherwise, it will cause short circuit and 

power cut-off by the circuit breaker; 

② 

Setting temperature by the thermostat(heating or cooling) should be within the temperature range of the 

product ;

③ 

For other constrains, please refer to previous pages about the remote air temperature sensor;

④ 

Do not connect external electric loads. Wire 220V AC(24V AC) and  220V GND(24V GND) should be 

used only for the electric thermostat.

⑤ 

Never connect external electric loads such as valves, fan coil units, etc. If connected, the mainboard of 

the unit can be seriously damaged.

⑥ 

Installation of the thermostat is very similar to that of the remote air temperature sensor.

4.14  Wiring of the Control

 

CN8

CN7

CN6

CN5

AP1

AP2

Wired controller

CN5

CN4

Long-distance

Minitor PC

Control Box

Notes:

 The wired controller can be connected to the terminal of AP1 CN6 or AP2 CN 8 through the four-wire 

communication line.

 AP1 (CN 5) and AP2 (CN 7) have been connected with the communication line (three-wire communication 

line before delivery. 

 The remote monitoring device can be connected to the CN4 of the wired controller through a four-wire 

communication line.

Summary of Contents for HLR10Pd/Na-K

Page 1: ...Change for life GREE ELECTRIC APPLIANCES INC OF ZHUHAI Mini Chiller Unit Installation eries...

Page 2: ...cation 6 4 4 Outline Dimension of the Mini Chiller 7 4 5 Installation Clearance Data 8 4 6 Electric Wiring 8 4 7 Wiring of the Terminal Board 9 4 8 Wiring of the 2 Way Valve 10 4 9 Wired Controller 11...

Page 3: ...kitchen or the plastic would be aged broken off or the polluted evaporator would lead to water leak and poor performance Do not place the unit where there is corrosive gas like sulfur dioxide or the...

Page 4: ...cording to installation manual 3 Do not connect to power until all installation work is completed 2 Filed Supplied Pipes and Valves Name Picture Usage Water Filter It is used to remove foreign matters...

Page 5: ...nstallation Examples CASE 1 Connection of Terminals for Heating and Cooling Under floor Loop Fan Coil Unit and Radiator B M Under Floor Coil FCU 1 T Radiator B T Bypass valve field supplied High tempe...

Page 6: ...maged The AC contactor control signal input terminal X17 AC contactor 1 and X18 AC contactor 2 of the main board AP1 should be connected to terminal 7 and terminal 8 of the electric box The single pin...

Page 7: ...Installation Diagramof the Electric Heater with the thermostat 2 See the following statement for installation of two groups of auxiliary electric heaters including wiring of the AC contactors and the...

Page 8: ...eet actual demands should be avoided Never open the electric box for wiring of the mainboard by the user themselves 4 2 Pre Installation 1 Installation of the unit must be in accordance with national...

Page 9: ...7 Unit Installation 4 4 Outline Dimension of the Mini Chiller HLR8Pd Na K HLR10Pd Na K 1390 412 361 388 890 HLR12Pd Na M HLR14Pd Na M 367 340 1390 1430...

Page 10: ...ng and moving must be 40 below to prevent center of the unit from moving 2 The monobloc unit should be installed on concrete base that is 10cm height 3 Requirements on installation space dimension of...

Page 11: ...9 Unit Installation HLR12Pd Na M HLR14Pd Na M 4 7 Wiring of the Terminal Board HLR8Pd Na K HLR10Pd Na K...

Page 12: ...ow Yes NC 2 wire 230V 50Hz 1Ph AC Closing water flow Yes Opening water flow Yes 1 Normal Open type When electric power is NOT supplied the valve is open When electric power is supplied the valve is cl...

Page 13: ...ram At the field installation it should be wired at the terminal board of the 2 way valve 1 4 9 Wired Controller Wired controller wiring guidance 4 10 Wiring of Other Auxiliary Heat Sources Other auxi...

Page 14: ...loor is approximately 1 5 meters Remote air temperature sensor can not be located where the area may be hidden when door is open Remote air temperature sensor can not be located where external thermal...

Page 15: ...e product For other constrains please refer to previous pages about the remote air temperature sensor Do not connect external electric loads Wire 220V AC 24V AC and 220V GND 24V GND should be used onl...

Page 16: ...g pipe proper 8 Are the nilometer of water tank water temperature indicator controller manometer pressure relief valve and automatic discharge valve etc installed and operated properly 9 Does power su...

Page 17: ...ce firstly Recheck the phase sequence before start up to avoid reverse rotation of the compressor which may damage the unit 4 Apply the universal electric meter to measure the insulation resistance be...

Page 18: ......

Reviews: