26
Technical Information
Service Manual
keeps the same.
◆
When air conditioner has a malfunction,dual-8 nixie tube will show relevant error code.
◆
When air conditioner defrosts automatically, dual-8 nixie tube displays “H1”. (Heating icon is bright for a period time and then OFF for
some models)
◆
If turn off light button, all display will be turned off.
(9) Memory function
①
Power failure when turning on the unit
◆
Memory content: ON status, mode, up&down swing, light, set temperature, set fan speed, general timer, Fahrenheit/ Celsius
◆
General timer can be memorized. Time of timer is calculated again from energization.
◆
Clock timer can’t be memorized.
②
Power failure when turning off the unit
◆
Memory content: OFF status, mode, up&down swing, light, set temperature, set fan speed, general timer, Fahrenheit/ Celsius
◆
General timer can be memorized. Time of timer is calculated again from energization.
◆
Clock timer can’t be memorized.
4. Special Function
(1) Health function (for the model with health function)
During operation of the IDU fan motor, press health button on the remote controller to start health function (If there is not health button on
the remote controller, the unit defaults health function ON).
(2) I Feel function (for all models, but it needs the remote controller which can set this function)
When I FEEL command is received, the controller will operate according to the ambient temperature sent by the remote controller (For
defrosting and cold air prevention, the unit operates according to the ambient temperature sensed by the air conditioner). The remote
controller will regularly send ambient temperature data to the controller. When the data has not been received for a long time, the unit
will operate according to the temperature sensed by the air conditioner. If I FEEL function is not set, the ambient temperature will be that
sensed by the air conditioner.
F1
Indoor ambient temperature sensor is open/
short-circuited
F2
Indoor evaporator temperature sensor is
open/short-circuited
H6
Blocked protection of IDU fan motor
C5
Malfunction protection of jumper cap
E5
Overcurrent protection
U8
Zero-crossing inspection circuit malfunction
of the IDU fan motor
Summary of Contents for GWC09MA-K3NNA3D
Page 56: ...53 Installation and Maintenance Service Manual GWH09MA K3NNA5F O...
Page 59: ...56 Installation and Maintenance Service Manual...
Page 60: ...57 Installation and Maintenance Service Manual...
Page 61: ...58 Installation and Maintenance Service Manual...
Page 62: ...59 Installation and Maintenance Service Manual...