DC Inverter U-match Series Duct Type Unit
6
Table 3
Size of Fitting
Pipe(Inch)
Max.
Pipe
Length
(m)
Max. Height
Difference between
Indoor Unit and
Outdoor Unit (m)
Drainage
pipe(Outer
Diameter × wall
thickness) (mm)
Liquid
Gas
GFH09K3FI GUHD09NK3FO
1/4
3/8
20
15
Φ20X1.2
GFH12K3FI GUHD12NK3FO
1/4
3/8
20
15
Φ30X1.5
GFH18K3FI GUHD18NK3FO
1/4
1/2
20
15
Φ30X1.5
GFH24K3FI GUHD24NK3FO
3/8
5/8
30
15
Φ20X1.2
GFH30K3FI GUHD30NK3FO
3/8
5/8
30
15
Φ20X1.2
GFH36K3FI GUHD36NK3FO
3/8
5/8
30
15
Φ20X1.2
GFH42K3FI GUHD42NK3FO
3/8
5/8
50
30
Φ20X1.2
GFH48K3FI GUHD48NK3FO
3/8
5/8
50
30
Φ20X1.2
GFH36K3FI GUHD36NM3FO
3/8
5/8
30
15
Φ20X1.2
GFH42K3FI GUHD42NM3FO
3/8
5/8
50
30
Φ20X1.2
GFH48K3FI GUHD48NM3FO
3/8
5/8
50
30
Φ20X1.2
GFH60K3FI GUHD60NM3FO
3/8
3/4
50
30
Φ20X1.2
① .
The connection pipe should be insulated with proper water-proof insulating material.
② .
The pipe wall thickness shall be 0.5-1.0mm and the pipe wall shall be able to withstand the
pressure of 6.0 MPa.The longer the connecting pipe, the lower the cooling and heating effect
performs.
3.4 Electrical Requirement
Electric Wire Size and Fuse Capacity.
Table 4
Indoor Units
Power Supply
Fuse Capacity
Breaker Capacity
Min. Power Supply
Cord
V/Ph/Hz
A
A
mm
2
09K~60K
220-240V~ 50Hz
5
6
1.0
Table 5
Model
Power
Supply
Capability of Air
Switch(A)
Minimum Sectional Area of Power Cable
and Earth line (mm
2
)
GUHD09NK3FO
220-240V
~
50Hz
13
1.5
GUHD12NK3FO
13
1.5
GUHD18NK3FO
16
1.5
GUHD24NK3FO
20
2.5
GUHD30NK3FO
20
2.5
GUHD36NK3FO
25
2.5
GUHD42NK3FO
25
2.5
GUHD48NK3FO
40
6.0
GUHD36NM3FO
380-415V 3N
~
50Hz
10
1.5
GUHD42NM3FO
10
1.5
GUHD48NM3FO
16
1.5
GUHD60NM3FO
16
1.5
Item
Model