GMV DC Inverter VRF
10
Based upon the actual conditions, if air handler is installed as Fig 4.2(A), the air handler
should be concealed in a specific room or space and make sure the air handler is not
accessible to the general public.
Based upon the actual conditions, if air handler is installed as Fig 4.2(B), make sure that
there is enough space for care and maintenance and the height between the air handler and
ground is above 2500mm. And the air handler is not accessible to the general public.
(A) (B)
Fig 4.2
4.3 Piping Work
4.3.1 Specification of Connection Pipe
Model
External Diameter (inch)
Gas Pipe(in)
Liquid Pipe(in)
GMV-ND24A/A-T(U)
5/8
3/8
GMV-ND30A/A-T(U)
5/8
3/8
GMV-ND36A/A-T(U)
5/8
3/8
GMV-ND42A/A-T(U)
5/8
3/8
GMV-ND48A/A-T(U)
5/8
3/8
GMV-ND54A/A-T(U)
5/8
3/8
4.3.2 Piping Preparation
All cut ends are to be round, burr free, and cleaned. Failure to follow this practice
increases the chances for refrigerant leakage.