Multi Variable Air Conditioners Concealed Floor Standing Unit
8
③
Above selection requirements: Power cord size is based on BV single-core wire (2~4pc) at
40
℃
ambient temperature when laying across plastic pipe. Air switch is D type and used at
40
℃
. If actual installation condition varies, please lower the capacity appropriately according
to the specifications of power cord and air switch provided by manufacturer.
④
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or
a similarly qualified person in order to avoid a hazard.
⑤
Install cut-off device near the unit. The minimum distance between each stage of cut-off device
should be 3mm (The same for both indoor unit and outdoor unit).
4 Installation Instructions
4.1 Installation of Indoor Unit
4.1.1 Outline Dimension and Installation Spots
Fig.4.1.1
Below are dimensions of A, B, C, etc. for different models:
Unit: mm
Model
A
B
C
D
E
F
GMV-ND22~36ZA/A-T
700
615
120
200
665.5
837
GMV-ND45ZA/A-T
900
615
120
200
865.5
1045
GMV-ND56~71ZA/A-T
1100
615
120
200
1065.5
1236
NOTE!
The height of ex-factory supporter is 120mm. If user wants to increase or decrease unit installation
height, please purchase the supporter of different height. Other height of supporter is 80mm, or 160mm.