Multi Variable Air Conditioners Ducted Type Indoor Unit
9
Fig 4.1.6
(5) Remove the washer locating plate and then tighten the nut on it.
Fig 4.1.7
4.2 Refrigerant Pipe Connection
(1) Aim the flaring port of copper pipe at the center of screwed joint and then tighten the
flaring nut with hand as shown in fig 4.2.
(2) Tighten the flaring nut with torque wrench.
Fig.4.2
(3) Use pipe bend when bending the pipe and the bending angle should not be too small.
(4) Wrap the connection pipe and joint with sponge and then tie them firmly with tape.
4.3 Installation of Indoor Unit
4.3.1 Outline Dimension and Installation Spots
(1) The drainage pipe should be short and the gradient downwards should be at least
1%~2% in order to drain condensation water smoothly.
(2) The diameter of drainage hose should be bigger or equal to the diameter of drainage
pipe joint.
(3) Install drainage pipe according to the following fig and arrange insulation to the