Multi Variable Air Conditioners Cassette Type Indoor Unit

 

22 

7 Table of Error Codes for Indoor Unit 

Error 

Code 

Content 

Error 

Code 

Content 

Error 

Code 

Content 

L0 

Indoor Unit Error 

LA 

Indoor Units Incompatibility 
Error 

d9 

Jumper Cap Error 

L1 

Indoor Fan Protection 

LH 

Low Air Quality Warning 

dA 

Indoor Unit Network Address 
Error 

L2 

E-heater Protection 

LC 

ODU-IDU Incompatibility 
Error 

dH 

Wired Controller PCB Error 

L3 

Water Full Protection 

d1 

Indoor Unit PCB Error 

dC 

Capacity DIP Switch Setting 
Error 

L4 

Wired Controller Power 
Supply Error 

d3 

Ambient Temperature 
Sensor Error 

dL 

Outlet Air Temperature 
Sensor Error 

L5 

Freeze protection 

d4 

Inlet Pipe Temperature 
Sensor Error 

dE 

Indoor Unit CO

2

 Sensor 

Error 

L7 

No Master Indoor Unit Error 

d6 

Outlet Pipe Temperature 
Sensor Error 

dy 

Water Temperature Sensor 
Error 

L8 

Power Insufficiency 
Protection 

d7 

Humidity Sensor Error 

C0 

Communication Error 

L9 

Quantity Of Group Control 
Indoor Units Setting Error 

d8 

Water Temperature Error 

AJ 

Filter Cleaning Reminder 

db 

Special Code: Field Debugging Code 

8 Troubleshooting 

The air conditioner is not expected to be serviced by users. Incorrect repair may cause electric 

shock or fire, so please contact an authorized service center for professional service. The following 
checks prior to contact may save your time and money.   

Phenomenon 

Troubleshooting 

The unit can’t start. 

 Power supply is not connected. 

 Circuit breaker tripping caused by leakage of electricity. 

 Input voltage is too low. 

 Defect of main PC-board. 

The unit stops after running 
for a while. 

 The inlet or outlet of ODU or IDU is blocked by obstacle. 

Poor cooling effect. 

 The filter is dirty. 

 Too heavy heat load of room (e.g. too many people). 

 Door or windows is open. 

 Inlet and outlet of IDU are blocked. 

 Setting temperature is too high. 

 Refrigerant is insufficient (e.g. refrigerant leakage). 

Poor heating effect. 

 The filter is dirty. 

 Door or window is open. 

 Setting temperature is too low. 

 Refrigerant is insufficient (e.g. refrigerant leakage). 

Indoor fan doesn’t start up 
during heating. 

 At starting, the IDU fan could not operate till the heat exchange become hot, for 

preventing delivering the cool air. 

 At defrosting, the IDU fan stopped due to system switch to cooling mode. For 

preventing delivering the cool air, and resume operating after defrosting. 

NOTE! 

If air conditioner still fails to work normally after checking and handling as described above, 

please stop using it immediately and contact local service center for assistance.

 

Summary of Contents for GMV-ND100T/A-T

Page 1: ...Multi Variable Air Conditioners Cassette Type Indoor Unit Models GMV ND28T A T GMV ND36T A T GMV ND45T A T GMV ND50T A T GMV ND56T A T GMV ND63T A T GMV ND71T A T GMV ND80T A T GMV ND90T A T GMV ND100...

Page 2: ...used for long cut off the power supply please energize and preheat the unit in advance before reusing it 3 Please properly select the model according to actual using environment otherwise it may impac...

Page 3: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Page 4: ...allation and Drainage System Testing 12 4 4 Panel Installation 15 4 5 Wired Controller Installation 16 5 Wiring Work 17 5 1 Connection of Wire and Patch Board Terminal 17 5 2 Power Cord Connection 18...

Page 5: ...to other units that have been confirmed as complying to corresponding partial unit requirements of this international standard The electrical interface shall comply with electrical security requiremen...

Page 6: ...objects into air outlet or air return grille If you use gas heater or petroleum heater in the same room please open the door or window to maintain good air circulation in case the room may lack of ox...

Page 7: ...onditioner by yourself Improper repair will cause electric shock or fire hazard Please contact GREE service center and have it repaired by professional technicians Any personal injury or property loss...

Page 8: ...d Cooling 27 19 35 24 Rated Heating 20 15 7 6 3 Preparations for Installation NOTE This picture is for reference only please refers to the actual product the unit of dimension is mm 3 1 Standard Fitti...

Page 9: ...The appliance shall not be installed in the laundry 2 The location should be able to withstand the weight of unit 3 The water can be drained conveniently from drainage pipe 4 There should be no obstru...

Page 10: ...f Communication Wire Selection NOTE If air conditioner used under strong electronic magnetic interference circumstance STP shielded twisted pair communication cable must be adopted 3 3 1 Selection of...

Page 11: ...power cord and capacity of air switch Model Power Cord Size Air Switch Capacity A Minimum Sectional Area of Ground Wire mm Minimum Sectional Area of Power Cord mm GMV ND28T A T 220 240V 1ph 50Hz 208...

Page 12: ...der to avoid a hazard The circuit breaker specification in above sheet is based on ambient temperature of 40 C If the working condition is different please adjust it according to the specification she...

Page 13: ...on position Drill 4 holes according to the hole site on the cardboard as shown in Fig 4 1 3 diameter of drilling hole is according to the diameter of expansion bolt and the depth is 60 70mm as shown i...

Page 14: ...pattern Refer to paper pattern of installation for ceiling opening dimension The center of ceiling opening is indicated on the paper pattern Fix the paper pattern to the unit with 4 screws and fix th...

Page 15: ...e Indoor Unit 11 Fig 4 1 6 4 2 Refrigerant Pipe Connection 1 Aim the flaring port of copper pipe at the center of screwed joint and then tighten the flaring nut with hand as shown in Fig 4 2 2 Tighten...

Page 16: ...e should be bigger or equal to the diameter of drainage pipe joint 6 Install drainage pipe according to the following fig and arrange insulation to the drainage pipe Improper installation may lead to...

Page 17: ...shaped joints 8 The installation height of raising pipe for drainage should be lower than B The gradient from raising pipe towards drainage direction should be at least 1 2 If the raising pipe is vert...

Page 18: ...over the electrical components e g water pump etc 1 In case of commissioning finished please energize the IDUs and switch to cooling or dry mode meanwhile the water pump operates you can check the dra...

Page 19: ...r decorative panel installation could cause the following problems Fig 4 4 1 2 Ensure that its clearance free between decoration panel and ceiling board after installation if not please adjust the bod...

Page 20: ...ing connection of signal receiver Notices that the connection wire not stuck in the middle of body and panel or may cause air leakage and lead to condensation water drop 4 Tighten 4 screws at each cor...

Page 21: ...munication wires should be separated from power cord and connection wire between indoor unit and outdoor unit Adjust the static pressure via wired controller according to site circumstance 5 1 Connect...

Page 22: ...holes 3 Connect the power cord to terminal L N 4 Fix the power cord with wiring clamp 5 3 Connection of Communication Wire between Indoor Unit and Outdoor Unit or indoor unit 1 Detach the electric bo...

Page 23: ...reless controller is shown as Fig 5 4 2 signal receiver is provided with panel as standard accessory Fig 5 4 1 Fig 5 4 2 2 Both IDU and wired controller are equipped with signal receiver and available...

Page 24: ...Multi Variable Air Conditioners Cassette Type Indoor Unit 20 Fig 5 5...

Page 25: ...the filter with a wet cloth dipped in neutral detergent Please contact after sales service staff if there is abnormal situation 6 1 Cleaning of Filter 1 Remove the filters from inlet of IDU Use a vac...

Page 26: ...repair may cause electric shock or fire so please contact an authorized service center for professional service The following checks prior to contact may save your time and money Phenomenon Troublesho...

Page 27: ......

Reviews: