DC Inverter Multi VRF System   

29 

Error 

Code 

Content 

Error 

Code 

Content 

FP 

Malfunction of DC motor   

J8 

High pressure ratio protection of system 

FU 

Malfunction of casing top temperature sensor of 

compressor 1 

J9 

Low pressure ratio protection of system 

Fb 

Malfunction of casing top temperature sensor of 

compressor 2 

JA 

Protection because of abnormal pressure 

Fd 

Malfunction of exit tube temperature sensor of 

mode exchanger     

JC 

Water flow switch protection 

Fn 

Malfunction of inlet tube temperature sensor of 

mode exchanger   

JL 

Protection because high pressure is too low   

b1 

Malfunction of outdoor ambient temperature 

sensor 

JE 

Oil-return pipe is blocked   

b2 

Malfunction of defrosting temperature sensor 1 

JF 

Oil-return pipe is leaking   

b3 

Malfunction of defrosting temperature sensor 2 

P0 

malfunction of driving board of compressor 

(uniform) 

b4 

Malfunction of liquid temperature sensor of 

sub-cooler 

P1 

Driving board of compressor operates 

abnormally (uniform) 

b5 

Malfunction of gas temperature sensor of 

sub-cooler 

P2 

Voltage protection of driving board power of 

compressor (uniform) 

b6 

Malfunction of inlet temp sensor of gas-liquid 

separator 

P3 

Reset protection of driving module of 

compressor 

b7 

Malfunction of outlet temp sensor of gas-liquid 

separator 

P4 

Drive PFC protection of compressor 

b8 

Malfunction of outdoor humidity sensor 

P5 

Over-current protection of inverter compressor 

b9 

Malfunction of gas temperature sensor of heat 

exchanger 

P6 

Drive IPM module protection of compressor 

bA 

Malfunction of oil-return temperature sensor 1 

P7 

Malfunction of drive temperature sensor of 

compressor 

bH 

Clock of system is abnormal 

P8 

Drive IPM high temperature protection of 

compressor 

bE 

Malfunction of inlet tube temperature sensor of 

condenser 

P9 

Desynchronizing protection of inverter 

compressor 

bF 

Malfunction of outlet tube temperature sensor of 

condenser 

PA 

Malfunction of drive storage chip of compressor 

bJ 

High-pressure sensor and low-pressure sensor 

are connected reversely 

PH 

High-voltage protection of compressor’s drive 

DC bus bar 

bP 

Malfunction of temperature sensor of oil-return 2 

PC 

Drive current detection circuit malfunction of 

compressor 

bU 

Malfunction of temperature sensor of oil return 3 

PL 

Low-voltage protection of compressor’s drive 

DC bus bar 

bb 

Malfunction of temperature sensor of oil return 4 

PE 

Phase-lacking of inverter compressor 

bd 

Malfunction of air inlet temperature sensor of 

subcooler 

PF 

Drive charging circuit malfunction of compressor 

bn 

Malfunction of liquid inlet temperature sensor of 

subcooler 

PJ 

Failure startup of inverter compressor 

H0 

Malfunction of driving board of fan (uniform) 

PP 

AC current protection of inverter compressor 

H1 

Driving board of fan operates abnormally 

(uniform) 

PU 

AC input voltage of drive of inverter compressor   

H2 

Voltage protection of driving board power of fan 

(uniform) 

G0 

PV reversed connection protection 

H3 

Reset protection of driving module of fan 

G1 

PV Anti-islanding protection 

H4 

Drive PFC protection of fan 

G2 

PV DC overcurrent protection 

H5 

Over-current protection of inverter fan 

G3 

PV power generation overload 

H6 

Drive IPM module protection of fan 

G4 

PV leakage current protection 

H7 

Malfunction of drive temperature sensor of fan 

G5 

Phase-lacking protection at power grid side 

H8 

Drive IPM high temperature protection of fan 

G6 

Phase-lacking protection at power grid side 

H9 

Desynchronizing protection of inverter fan 

G7 

PV LVRT 

HA 

Malfunction of drive storage chip of inverter 

outdoor fan 

G8 

Overcurrent protection at power grid side 

HH 

High-voltage protection of fan’s drive DC bus bar 

G9 

Drive IPM module protection at power grid side 

HC 

Drive current detection circuit malfunction of fan 

GA 

Low/high input voltage protection at power grid 

side 

HL 

Low-voltage protection of fan’s drive DC bus bar 

GH 

Photovoltaic DC\DC protection 

Summary of Contents for GMV-36WL/C-T

Page 1: ...Owner s Manual Original Instructions Commercial Air Conditioners DC Inverter Multi VRF System Applicable Models GMV 60WL C T U GMV 48WL C T U GMV 36WL C T U...

Page 2: ...All graphics in this manual is only for your reference For sales or production reasons these graphics are subject to change by manufacturer without prior notice 9 This appliance is not intended for u...

Page 3: ...Hole 5 4 2 Connection Pipe 6 4 3 Installation of Connection Pipe 10 4 4 Disassembly of Compressor Feet 14 4 5 Vacuum Pumping Refrigerant Adding 15 4 6 Electric Wiring 17 5 Check Items after Installati...

Page 4: ...ephone line 6 Be sure to use special accessories and parts for installation to prevent water leakage electric shock and fire hazard etc 7 If refrigerant leakage happens please ventilate the room immed...

Page 5: ...tely and then contact Gree appointed service center If those abnormal circumstances still exit the unit may be damaged and it may lead to electric shock or fire hazard 27 Do not repair the unit by you...

Page 6: ...s of DC Inverter Multi VRF System can be connected to various indoor units When any one of the indoor units receives operating command outdoor unit will start operation as per required capacity When a...

Page 7: ...for heat exchange and maintenance so that unit can operate reliably with good ventilation 7 Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with go...

Page 8: ...r piping work requirements R410A Refrigerant System Outer diameter mm inch Wall thickness mm inch 6 35 1 4 0 8 1 32 9 52 3 8 0 8 1 32 12 7 1 2 0 8 1 32 15 9 5 8 1 0 1 25 19 05 3 4 1 0 1 25 4 Installat...

Page 9: ...inch Model A B C D E GMV 36WL C T U GMV 48WL C T U 900 35 3 8 340 13 3 8 1345 53 572 22 1 2 378 15 GMV 60WL C T U 940 37 320 12 9 16 1430 56 1 4 632 24 7 8 350 14 7 8 4 2 Connection Pipe 4 2 1 Schemat...

Page 10: ...and Height Difference of Connection Pipe Piping parameters of GMV 36WL C T U GMV 48WL C T U GMV 60WL C T U Allowable value Fitting pipe m feet Total length actual length of fitting pipe 300 984 L1 L2...

Page 11: ...le Pipe dimension Gas pipe mm inch Liquid pipe mm inch GMV 36WL C T U 15 9 5 8 9 52 3 8 GMV 48WL C T U 15 9 5 8 9 52 3 8 GMV 60WL C T U 19 05 3 4 9 52 3 8 4 2 4 Selection of Indoor Branches Select ind...

Page 12: ...otal capacity of downstream indoor units C Btu h Pipe mm inch Liquid pipe mm inch C 19000 12 7 1 2 6 35 1 4 19000 C 48500 15 9 5 8 9 52 3 8 48500 C 76400 19 05 3 4 9 52 3 8 4 2 6 Dimension of Pipe bet...

Page 13: ...le is not allowed 3 When laying the pipe be careful not to distort it Radius of bending parts should be over 200mm 8inch Note that pipes cannot be repeatedly bent or stretched otherwise the material w...

Page 14: ...of nut will get damaged if the flared nut is twisted forcibly 3 Use torque wrench to twist on the flared nut tightly until the wrench gives out a click sound Hold the handle of wrench and make it at r...

Page 15: ...ht or rear side Fig 4 13 2 Pipe connection for GMV 60WL C T U As shown in Fig 4 14 and Fig 4 15 open the outermost soundproof cotton and place a fire barrier between compressor and straight pipe Use a...

Page 16: ...d remove burrs as well See Fig 4 17 3 Y type branch must be installed vertically or horizontally Fig 4 17 Branch shall be isolated by insulating material that can bear 120 C 248 F or even higher tempe...

Page 17: ...perature For heat pump unit liquid pipe should bear 70 C 158 F or above and gas pipe should bear 120 C 248 F or above For cooling only unit both liquid pipe and gas pipe should bear 70 C 158 F or abov...

Page 18: ...ds to be charged with additional refrigerant 2 Confirm whether outdoor liquid and gas valves are closed 3 Use vacuum pump to withdraw the air inside indoor unit and connection pipe from the outdoor va...

Page 19: ...Quantity of IDU 2 0 3 kg 10 58oz First confirm that there is no leakage from the system When compressor is not working charge additional R410A with specific amount to the unit through the filling ope...

Page 20: ...function and thermal trip function so that system can be protected from short circuit and overload 6 Air conditioner belongs to class I electrical appliance so it must be securely grounded 7 The yell...

Page 21: ...ot being supplied to the indoor unit and outdoor unit 2 Match the terminal block numbers and connection cord colors with those of the indoor unit side Erroneous wiring may cause burning of the electri...

Page 22: ...condition changes please adjust the specification according to national standard 3 Specification of circuit breaker is based on the working condition where ambient temperature of circuit breaker is 40...

Page 23: ...DC Inverter Multi VRF System 20 Fig 4 26 Fig 4 27...

Page 24: ...placing the main board of outdoor unit it is necessary to perform test operation and debugging Otherwise unit won t be able to work 2 Test operation and debugging must be performed by professional tec...

Page 25: ...mmunication wire of IDU is correctly connected After the check connect power and start debugging from progress 01 If the number is then correct press main board s SW3 button to confirm Then the displa...

Page 26: ...ts 08_ Confirm preheated compressor 08 U0 Display circularly Preheat time for compressor is less than 8 hours Display will be as in the left until the preheat time reaches 8 hours Press main board s S...

Page 27: ...in this process through the L VALVE 15_ Cooling debugging 15 AC Display circularly Debugging for cooling mode If no malfunction occurs for 50min when compressor is running then the system is certifie...

Page 28: ...ient temp is 25 35 C 77 95 F in cool mode system s high pressure value will be within 44 53 C 111 127 F In heat mode if ambient temp is above 5 C 23 F system s high pressure value is within 40 52 C 10...

Page 29: ...or EXV varies within 40 480PLS 15 Communication parameters Communication data Number of IDUs detected by software is the same with the actual number No communication error 16 Drainage system Indoor un...

Page 30: ...locked and dirty Clean the filter If problem cannot be solved after checking the above items please contact Gree service center and describe the cases and models Following circumstances are not malfun...

Page 31: ...rossing malfunction of PG motor dU Malfunction of drainage pipe temperature sensor of generator LU Indoor unit s branch is not inconsistent for one to more unit of heat recovery system db Debugging st...

Page 32: ...of outlet tube temperature sensor of condenser PA Malfunction of drive storage chip of compressor bJ High pressure sensor and low pressure sensor are connected reversely PH High voltage protection of...

Page 33: ...en main control and DC DC controller U6 Alarm because valve is abnormal C2 Communication malfunction between main control and inverter compressor driver U7 Power grid DRED0 response protection C3 Comm...

Page 34: ...connection pipe of ODU An Child lock status Ay Shielding status 8 Maintenance and Care Regular check maintenance and care can extend unit s service life Please have specialized person in charge of the...

Page 35: ...ix oxygen C2H2 or other dangerous gas into the refrigerant circuit Otherwise it may lead to danger Use nitrogen or refrigerant to conduct the tests 9 After sales Service If there s quality defect or o...

Page 36: ......

Reviews: