Gree GMV6 DC Inverter VRF Units Service Manual
320
Appendix 4 Electric Specifications
Every unit should have corresponding short-circuit and overload protection. And also a main switch
is required to control Power or disconnection.
Please refer to the following table for the leakage protection switch and circuit breaker of outdoor
unit.
Outdoor units Combination
Power
Fuse Capacity Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
Cross-sectional
Area of Power
Cable Conductor
V/Ph/Hz
A
A
A
mm²
GMV-
224WM/G-U
—
440~460V
3~ 60Hz
25
19.6
25
4*4.0
GMV-
280WM/G-U
—
440~460V
3~ 60Hz
25
20
25
4*4.0
GMV-
335WM/G-U
—
440~460V
3~ 60Hz
30
21
30
4*4.0
GMV-
400WM/G-U
—
440~460V
3~ 60Hz
30
23.9
30
4*4.0
GMV-
450WM/G-U
—
440~460V
3~ 60Hz
30
24.2
30
4*4.0
GMV-
504WM/G-U
—
440~460V
3~ 60Hz
30
25
30
4*4.0
GMV-
560WM/G-U
—
440~460V
3~ 60Hz
40
36.2
40
4*6.0
GMV-
615WM/G-U
—
440~460V
3~ 60Hz
40
38
40
4*6.0
GMV-
680WM/G-U
—
440~460V
3~ 60Hz
45
40.9
45
4*10.0
GMV-
735WM/G-U
335+400 440~460V
3~ 60Hz
20+30
21.0+23.9
20+30
4*4.0+4*4.0
GMV-
785WM/G-U
335+450 440~460V
3~ 60Hz
20+30
21.0+24.2
20+30
4*4.0+4*4.0
GMV-
839WM/G-U
335+504 440~460V
3~ 60Hz
20+30
21.0+25.0
20+30
4*4.0+4*4.0
GMV-
895WM/G-U
280+615 440~460V
3~ 60Hz
20+40
20.0+38.0
20+40
4*4.0+4*6.0
GMV-
950WM/G-U
335+615 440~460V
3~ 60Hz
20+40
21.0+38.0
20+40
4*4.0+4*6.0
GMV-
1015WM/G-U 400+615
440~460V
3~ 60Hz
30+40
23.9+38.0
30+40
4*4.0+4*6.0
GMV-
1064WM/G-U 504+560
440~460V
3~ 60Hz
30+40
25.0+36.2
30+40
4*4.0+4*6.0
GMV-
1119WM/G-U 504+615
440~460V
3~ 60Hz
30+40
25.0+38.0
30+40
4*4.0+4*6.0
GMV-
1175WM/G-U 560+615
440~460V
3~ 60Hz
40+40
36.2+38.0
40+40
4*6.0+4*6.0