INSTALLATION INSTRUCTIONS
34
Filling the refrigerant
Safety instructions for transportation and storage
a. Shut down the unit and cut power supply
b. Eliminate the refrigerant
c. Vacuuming
d. Clean it with N2 gas
e. Cutting or welding
f. Carry back to the service spot for welding
The refrigerant should be recycled into the specialized storage tank.
Make sure that there isn’t any naked flame near the outlet of the vacuum pump
and it’s well-ventilated.
Use the refrigerant filling appliances specialized for R32. Make sure that different
kinds of refrigerant won’t contaminate with each other.
After filling is finished, please do the leakage detection before test running; another
time of leak detection should be done when it’s removed.
Please use the flammable gas detector to check before unload and open the container.
No fire source and smoking.
According to the local rules and laws.
The refrigerant tank should be kept upright at the time of filling refrigerant.
Stick the label on the system after filling is finished (or haven’t finished).
Don’t overfilling.
Safety operation of flammable refrigerant
Summary of Contents for GEH09AA-K6DNA1F/I
Page 2: ...GEH09AA K6DNA1F I GEH12AA K6DNA1A I GEH18AA K6DNA1F I...
Page 39: ......
Page 40: ...66129931224...
Page 42: ......
Page 43: ...GEH09AA K6DNA1F O GEH12AA K6DNA1A O GEH18AA K6DNA1F O...
Page 67: ......
Page 68: ...66129931225...
Page 70: ...GEH09AA K6DNA1F I GEH12AA K6DNA1A I GEH18AA K6DNA1F I...
Page 108: ...GEH09AA K6DNA1F O GEH12AA K6DNA1A O GEH18AA K6DNA1F O...
Page 134: ...GEH09AA K6DNA1F I GEH12AA K6DNA1A I GEH18AA K6DNA1F I...
Page 170: ......
Page 171: ......
Page 174: ...GEH09AA K6DNA1F O GEH12AA K6DNA1A O GEH18AA K6DNA1F O...