Wiring
With a Multi indoor unit, install as described in the installation manual supplied with the Multi outdoor unit.
Live the sensor securing plate, remove the front metal plate cover, and connect the branch wiring to the terminal block.
1)Strip wire ends (15mm)
2)Mach wire colours with terminal numbers on indoor and outdoor unit’s terminal blocks and firmly screw wires to
the corresponding terminals.
3)Connect the earth wires to the corresponding terminals.
4)Pull wires to make sure that they are securely latches up, then retain wires with wire retainer.
CAUTION
1)Do not use tapped wires, stranded wires, extensioncords, or starburst connections, as they may cause overheating,
electrical shock, or fire.
2)Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc, from
the terminal block.) Doing so may cause electric shock or fire.)
Appliance shall be installed, operated and stored in a room with a floor area
Please notice that the unit is filled with flammable gas R32. Inappropriate
larger than Xm .
treatment of the unit involves the risk of severe damages of people and
material. Details to this refrigerant are found in chapter “refrigerant”.
2
(Please refer to table "a" in section of " Safety Operation of Inflammable Refrigerant" for Space X.)
2
7
INSTALLATION INSTRUCTIONS
Installation of indoor unit
Outdoor unit
Indoor unit
Firmly fix the wires with the
terminal screws
Firmly fix the wires with the
terminal screws
When wire length exceeds 10m,
use 2.0mmdiameter wires
N(1) 2
3
Terminal block
Electrical
component
box
Wire retainer
Use the specified wire type.
Shape wires so
that the front metal
plate cover will fit
securely.
Firmly secure wire
retainer so that
wires sustain no
external stress.
Sensor securing plate
Front metal
plate cover
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.