6.3 Function Introduction
1 Applicable Range
This is suitable for top discharge window type units.
2 Basic Functions
2.1 Cooling Mode
2.1.1 Working Conditions and Process of Cooling
a) when T
abm.
≥T
preset
+2°F (1°C ), the unit is running in cooling mode. The compressor is started
and the fan will run at setting speed.
b) when T
abm.
≤T
preset
-2 °F(1°C ), the compressor will be stopped while the indoor fan will run
at setting speed.
c) when T
preset
-2 °F(1 °C)
<
T
abm.
<
T
preset
+2 °F(1 °C), the unit will keep previous running status
2.1.2 In this mode, the temperature setting range is 61°F~86°F (16°C~30 °C).
2.2 Energy Saving Mode
2.2.1 Working conditions and process of energy saving
a) When T
abm.
≥T
preset
+2°F (1 °C), the compressor will be started and the fan will run at the setting speed.
b) When T
abm
≤T
preset
-2°F (1°C ),the compressor will be stopped, and the indoor fan will also be stopped after running at setting speed
for 60s.
c) When T
preset
-2°F (1 °C)
<
T
abm.
<
T
preset
+2 °F(1°C ),the unit will keep previous running status.
d) When the unit turn to the energy saving mode at the first time and compressor is OFF, then the indoor fan will be stopped after
running at setting speed for 1 min.
2.2.2 In this mode, the temperature setting range is 61°F~ 86°F( 16 °C~30°C) .
2.3 Fan Mode
2.3.1 In this mode, the compressor will be stopped while the fan is running at setting speed.
2.3.2 In this mode, the FAN MODE LED is bright and temperature is unadjustable.
2.3.3 In this mode, there isn’t auto fan. If the previous working mode is the fan mode switched from auto fan , it will run at high speed
when it turns to fan mode at the first time.
2.4 .Heating Mode
2.4.1.Heating Conditions and Process (compressor and heat electric can’t run at the same time)
A. Heat pump and electric heating unit
1. When T
prenest
-5°F (3°C) < T
amb.
≤ T
prenest
-2°F (1°C), the compressor will run to heat, meanwhile, the 4-way valve, indoor fan motor,
outdoor fan motor and compressor will operate. When T
amb
≤ T
preset
-5°F (3°C) also satisfied compressor running and the minimum
operation time of compressor, compressor and outdoor fan motor stops, electric heater is on 1S later. Once electric heating mode
operation, it will set out when it meet 2 conditions(except protection function). When the compressor have heating demand (T
preset
-5°F
(3°C) < T
amb.
≤ T
preset
-2°F (1°C) ), when the compressor can’t set on due to protection function, electric heater will instead of compressor
for heating after 15S until meet temp then stops. When T
amb
≤ T
preset
-5°F(3°C), electric heating mode will runs, indoor fan motor runs
refer to setting temp.
2. When T
amb
≥ T
preset
+2°F (1°C), the compressor or electric heater stops, the indoor fan motor runs refer to setting fan speed and stops
1 minute later.
3. When T
preset
-2°F < T
amb.
< T
preset
+2°F (1°C), the unit will maintain its original status.
B. Electric heating unit
a) When T
abm.
≤ T
preset
-2°F (1°C), the electric heating is running and the indoor fan will run at setting speed.
b) When T
abm.
≥ T
preset
+2°F (1°C),the electric heating is OFF, and indoor fan will be stopped after running at setting speed for 1 min.
c) WhenT
preset
-2°F<T
abm.
<T
preset
+2°F (1°C), the unit will keep previous running status.
2.4.2 In this mode, the temperature setting range is 61°F~86°F(16°C~30°C).
3 Other Functions
3.1 Buzzer
When energization and operation, the buzzer will give out a beep.
3.2 Sleep
a) In cooling and energy saving mode, the setting temperature will increase by 2°F (1 °C) in 1 hour after sleep setting and increase by 4°F
(2°C ) in total in 2 hours. After this 2 hours , the setting temperature won’t increase any more and t he temperature setting upper limit is
86°F (30°C )
b) In heating mode, the setting temperature will decrease by 2°F (1°C ) in 1 hour after sleep settingand decrease by 4°F (2°C ) in total
in 2 hours. After this 2 hours, the setting temperature won’t decrease any more and the temperature setting lower limit is 61°F (16 °C)