![Gree FP-102XD/B-T Owner'S Manual Download Page 17](http://html1.mh-extra.com/html/gree/fp-102xd-b-t/fp-102xd-b-t_owners-manual_2260630017.webp)
Cassette Type Fan Coil Unit
14
Fig.26
Attention:
The Wired controller, Remote control system and Gate control systemare the optional
accessories.
The maximal capacity of the output signal CN6 or CN24 of the water valve is 5A.
The broken lines is for field connection.
10 Installation of the panel
Note:The FCUs can be equipped with panel.
(1) Set the panel to the unit body by matching the posotion of the swing flap motor of the
decoration panel to the piping position of the panel to the piping position of the unit as shown in
Fig.27.
(2) Install the decoration pannel.
1)
Hang the latch, which is located on the opposite side of the swing flap motor on the panel,
temporarily to the book of the unit. (2 positions)
2) Temporarily hang the remaining 2 latches to books on the sides of the unit. (be careful not to let
the swing motor lead wire get caught in the sealing material.)
3) Screw all 4 hexagon head screws located right beneath the latches in approximately 15 mm.
(panel will rise)
4)
Adjust the panel by turning it to the arrowed direction in Fig.28 so that the ceiling opening is
completely covered.
5) Tighten the screws unitl the thickness of the sealing material between the panel and the unit
body is reduced to 5~8 mm.