Gree FP-102XD/B-T Owner'S Manual Download Page 11

Cassette Type Fan Coil Unit

8

1-1.5m

(Correct) 1/100 ro more gradient

(Wrong)

Fig.9

(5) Use the attached drainage hose and clamp.Insert the drainage hose into the drainage socket 

up to the grey tape(as Fig.10).

(6) Tighten the clamp until the screw head is less thean 4 mm from the hose(as Fig.10).
(7) Wrap the big sealing pad around clamp of the drainage hose to insulate.
(8) Insulate the drainage hose inside the room.

Sponge(attachment)

Clamp(attachment)

Clamp

Below 4mm

Sponge(gray) Drain hose

Fig.10

 Precoutions for drainage raising pipe

(1) Install the drainage raising pipe at a height of less than 280 mm(as Fig.11).
(2) Install the drainage raising pipe at a right angle to the unit and no more than 300 mm from the 

unit.

below500mm

.

Within 300mm

Drain raising 

hose

220mm

 Ceiling

Clamp(attachment)

Hoisting stand

Roof

Drain hose

(attachment)

1-1.5m

below

280mm

Fig.11

Instruction The slant gradient of the attached drain hose should be within 75mm so that the 

drain hole doesn’t has to endure the unnecessary outside force(as Fig.12). 

below

500m

m

.

below75m

m

Drain hose(attachment)

Fig.12

Summary of Contents for FP-102XD/B-T

Page 1: ...140XDS B T FP 140XDM B T FP 140XDSM B T FP 160XD B T FP 160XDS B T FP 160XDM B T FP 160XDSM B T FP 180XD B T FP 180XDS B T FP 180XDM B T FP 180XDSM B T FP 200XD B T FP 200XDS B T FP 200XDM B T FP 200X...

Page 2: ...l DISPOSAL This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled w...

Page 3: ...4 Name of the front panel 3 5 Installation of the unit 4 6 Drainage pipe 7 7 Connecting the pipes 9 8 Motorized valve 10 9 Electric wiring 12 10 Installation of the panel 14 11 Check after installatio...

Page 4: ...wrong repair will lead to an electric shock or fire you contact the service center repair The appliance shall be disconnected from its power source during service and when replacing parts 1 1 Importan...

Page 5: ...and rated value should refer to the silk screen on the controller or fuse sleeve 3 The appliance shall be installed in accordance with national wiring regulations 4 After the field commissioning the w...

Page 6: ...The built in air filter removes dust and dirty Air outlet Chilled water piping Connection electric wire Drain pipe Drainage device built in remove water from the unit during cooling Fig 1 4 Name of th...

Page 7: ...button over 5 seconds the unit run 2 At stopping When the unit is running pressed AUTO button and overrun 5 seconds the unit stop 3 When the unit is running pressed AUTO button less than 5 seconds The...

Page 8: ...h space for care and maintenance Make sure that the height between the unit and ground is above 2500 mm 6 When installing the suspender bolt check if the install place can stand the weight 4 times of...

Page 9: ...isting screw 4 Water pipe 780 Gaps between hoisting screw rods 840 Indoor unit 890 Ceiling opening 950 Decorated surface boards Fig 6 The drilling of holes in the ceiling must be done by the professio...

Page 10: ...et vent by bolt 3 Adjust the unit to the suitable install place as Fig 8 4 Check if the unit is horizontal as Fig 8 Inner drainage pump and bobber switch are included in the unit check if 4 angle of e...

Page 11: ...ttachment Clamp Below 4mm Sponge gray Drain hose Fig 10 Precoutions for drainage raising pipe 1 Install the drainage raising pipe at a height of less than 280 mm as Fig 11 2 Install the drainage raisi...

Page 12: ...r inspection hole slowly and check drainage flow as Fig 14 Way of immiting Drain hose Test hole cover Test hole Above100mm Drain vent for repair use plastic stopper is included drain the water in wate...

Page 13: ...water valve wire and sponge up with the copper tube as there would be probably a short circuit or even electric leakage The right way is letting the water valve wire go through the pipe sleeve and the...

Page 14: ...e installation both the torque wrench and the spanner should be used and the moment of torque should be within 90 N m Besides a secure connection should be guaranteed Flare nut Wiring interface water...

Page 15: ...n a fire hazard as Fig 22 Fig 22 The right way is placing the valve core in the proper position and letting the leading wire pointing at the unit as Fig 23 Fig 23 Sponge It is prohibited to wrap the w...

Page 16: ...be installed in accordance with national wiring regulations the WIRING DIAGRAM in the manual is reference The correct wiring should agree with the WIRING DIAGRAM on controller box of the unit 1 Remov...

Page 17: ...unit as shown in Fig 27 2 Install the decoration pannel 1 Hang the latch which is located on the opposite side of the swing flap motor on the panel temporarily to the book of the unit 2 positions 2 T...

Page 18: ...tte Type Fan Coil Unit 15 The connecting pipe shoulde be located corresponding to the marking Fig 27 Piping position Hook Swing flap motor Latch Unit Air outlet Panel 5 8mm Sealing material Ceiling Fi...

Page 19: ...t body Refer to Fig 30 No gap is allowed Adjustment of the indoor unit body from the holes in the corner of the panel is possible if the indooor unit is kept leveled and the drainage pipe piping etc i...

Page 20: ...ireless remoter controller 11 2 1 Before test operation 1 Do not switch on power before installation is finished completely 2 Electric wiring must be connected correctly and securely 3 All the impurit...

Page 21: ...33 Open the buckle slinghtly by hand Loosen the screw under the buckle with a screw driver Fig 34 Lift up the grill by clutching it through the holes with the finger the left finger acts first Fig 35...

Page 22: ...uction grille Set air filter by sliding the knob the back of the suction grille inward 5 Shut the suction grille Refer to step 1 How to clean the suction grille 1 Open the suction grille See step 1 of...

Page 23: ...50x85 If there is any change we will not give you notice here the correct parameters is in the nameplate of your FCU The FCU designed for installation indoor The environmental temperature is from 5 C...

Page 24: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com...

Reviews: