5 Blower Speed Selection
Proper air volume must be provided over the evaporator coil. Select a blower
motor speed tap that will provide 300-450 CFM per 12,000 Btu/h of cooling capacity
(wet coil). Recommended air flow volume as shown in Table 1.
Table 1
Cabinet
Recommended Vol(CFM)
Model
Width(in.)
17.5
800
17.5
1000
24.5
1230
24.5
1510
6 Maintenance and Care
Regular check, maintenance and care should be performed by professional
personnel, which will prolong the unit life span.
6.1 Drain Pipe
Regularly check if the drain pipe is clogged in order to drain condensate smoothly.
6.2 Notice before Seasonal Use
(1) Check if the inlet/outlet of the indoor unit is clogged.
(2) Check if the filter screen has been set soundly.
(3) Check if the unit is installed firmly. If there is something abnormal, please contact
the local appointed service center.
6.3 Maintenance after Seasonal Use
(1) Clean the dust of sundries on the indoor units.
(2) In the event of rusting, use the anti-rust paint to stop spreading of rust.
6.4 Parts Replacement
Purchase parts from local appointed service center or dealer if necessary.