6.1.1 Temperature Parameters
Indoor preset temperature (T
preset
)
Indoor ambient temperature (T
amb.
)
6.1.2 Basic Functions
Once energized, the compressor should in no way be restarted unless after 3-minute time interval at least. For the first
energization, the compressor will be started without 3-minute lag. Once started, the compressor will not be stopped
within 6 minutes with the change of room temperature.
6.1.2.1 Cooling Mode
6.1.2.1.1 Working Conditions and Process of Cooling
When T
amb
.
≥
T
preset
+1
℃
, the unit will run under cooling mode, in which case the compressor and outdoor fan will start
and the indoor fan will run at preset speed.
When T
amb.
≤
T
preset
-1
℃
, the compressor and the outdoor fan will be stopped, the indoor fan will run at preset speed.
When T
preset
-1 <T
℃
amb.
< T
preset
+1 , the unit will maintain its original operating status.
℃
After startup of unit under or to cooling mode from other mode when ambient temp 30 , or amibient temp is 3 higher
or much higher than setting temp , indoor fan after startup of compressor will be forced to run at super high speed and
T
preset
+1
℃
T
preset
-1
℃
Start cooling
Original operating status
Stop cooling
≥
6 min.
≥
6 min.
≥
3 min.
T
amb
Compressor
Outdoor fan
Indoor fan
Preset speed
Run
Stop
6.1.2.1.2 Pretection
Antifreezing Protection
If it is detected that the system is under antifreeze protection,E2 will be displayed, the compressor and outdoor fan
will be stopped, and the indoor fan will run at preset speed. When antifreeze protection is released and the compressor
has been stopped for 3 minutes,LCD display will resume, and the unit will resume its original operating status.(Buttons are
not shielded during defrosting protection.)
During antifreeze protection
Preset speed
Run
Stop
Compressor
Outdoor fan
Indoor fan
≥
3 min.
Overcurrent Protection
If it is detected that the system amperage exceeds the specified value(about 22 A), the unit will stop when indoor ambient
temp reaches setting temp.If the compressor has been stopped for 3 minutes and it is detected that the system's current
resumes normal, the unit will resume original running state.If protection time is over 6, LED will blink and display E5, in which case,
original running state can't resume, so it is needed to press ON/OFF button to stop and then repress this button to restart the
unit.
6
6
6
6
6
Remote Controller Function Manual and Operating Instruction
Remote Controller Function Manual
6
6
6
6
6
≥ ℃
℃
then switch into setting speed after 10 min or after temp reaches so that the unit stops.Once indoor fan runs at setting
speed after startup of compressor, it won't be forced to run at super high speed.Under this mode, switchover valve is
de-energized and temp range is 16-30 .
25
Summary of Contents for Cooling Bay GVCN18AANK1A1A
Page 2: ...Model Remarks 36K 48K outdoor unit...
Page 15: ...3 Air outlet Component Name Cooling Bay Series...
Page 20: ...5 Electrical Diagram...
Page 21: ...Cooling Bay Series...
Page 47: ...8 Exploded View and Components and Parts List Exploded View of Indoor Unit Cooling Bay Series...
Page 49: ...Exploded View of Indoor Unit Cooling Bay Series...
Page 51: ...Exploded View of Indoor Unit Cooling Bay Series...
Page 58: ...Exploded View of Outdoor Unit...
Page 61: ...Exploded View of Outdoor Unit Cooling Bay Series...
Page 65: ...Exploded View of Outdoor Unit Cooling Bay Series...
Page 68: ...Exploded View of Outdoor Unit...