41
Installation and Maintenance
Service Manual
9.1 Error Code List
9. Maintenance
No. Malfunction
Name
Display Method
of Indoor Unit
(Error Code)
A/C Status
Possible Causes(For specific maintenance
method, please refer to the following procedure of
troubleshooting)
1
Indoor ambient
temperature
sensor is
open/short-
circuited
F1
The unit will stop operation as it
reaches the temperature point.
During cooling and drying operation,
except IDU fan motor operates, other
loads stop operation; During heating
operation, the system stops operation.
1.The wiring terminal between indoor ambient temperature
sensor and main board is loosened or poorly contacted;
2.There’s short circuit due to trip-over of the parts on
controller;
3.Indoor ambient temperature sensor is damaged (Please
check it by referring to the resistance table for temperature
sensor)
4. Main board is broken.
2
Indoor
evaporator
temperature
sensor is
open/short-
circuited
F2
The unit will stop operation as it
reaches the temperature point.
During cooling and drying operation,
except IDU fan operates, other
loads stop operation; During heating
operation, the complete unit stops
operation.
1.The wiring terminal between indoor evaporator
temperature sensor and main board is loosened or poorly
contacted;
2.There’s short circuit due to the trip-over of the parts on
controller;
3.Indoor evaporator temperature sensor is damaged
(Please check it by referring to the resistance table for
temperature sensor)
4. Main board is broken.
3
Blocked
protection of
IDU fan motor
H6
IDU fan, ODU fan, compressor and
electric heat tube stop operation.
Horizontal louver stops at the current
position.
1.The feedback terminal of PG motor is not connected
tightly.
2.The control terminal of PG motor is not connected tightly.
3.Fan blade rotates unsmoothly.
4.Malfunction of motor
5.Main board is broken.
4
Malfunction
protection of
jumper cap
C5
Operation of remote controller or
control panel is available, but the unit
won’t act.
1.There’s not jumper cap on the main board.
2.Jumper cap is not inserted properly and tightly.
3.Jumper cap is damaged.
4.Controller is damaged.
5
Overload
malfunction
E8
The entire unit stops.
1.Indoor and outdoor heat exchanger is too dirty?
Or air inlet/outlet is blocked?
2.Fan motor doesn't work at a normal fan speed; fan
speed is too low or the fan doesn't run.
3.Compressor operates normally or not? Is there any
abnormal noise or oil leak? Casing is too hot?
4.System is blocked inside? (Dirt blockage? Ice blockage?
Oil blockage? Y-valve is not fully open?)
5.Main board temperature sensor detects wrongly.