Fig. 56 Engine ignition
Note:
•
Wait for 20 to 30 seconds between 2
startup attempts.
•
Do not turn the key when the engine is
running.
6.2.4 In case of push button start
•
Press the push button. Release
immediately when the engine picks up
speed.
Note:
•
Do not push the button when the engine is
running.
•
Wait for 20 to 30 seconds between 2
startup attempts.
6.2.5 AMF operation start up
•
In case of Auto Mains Failure (AMF) mode
operation of power generation application,
the engine starts automatically when the
grid power fails.
•
It is extremely important to inform
everybody that genset is in AMF mode.
•
Access to area nearby genset should be
avoided as the engine can start
automatically without notice.
•
In case of maintenance, it is necessary to
put the engine in non-AMF mode and
remove battery cables before starting
maintenance.
6.3 Stopping the engine
•
Remove the load from the engine.
•
Run for 2 minutes to stabilize the
temperatures.
Recommended for
turbocharged and turbo after cooled
engines.
•
Push the stop button to stop the engine.
•
The engine can also be stopped manually
by turning the stop lever on the fuel pump
(Photo STOP lever on fuel pump).
Fig. 57 Fuel Stop Valve
Turn the key to “Off” mode so that battery does not
get depleted / discharged.
6.4 Safety stop
The engine will automatically stop in case of
certain safety conditions like
•
High water temperature
•
Low lube oil pressure
Check the reason for this event before trying to
restart. Do not restart, till the event is completely
explained and corrective action is taken. Never
bypass safeties or try to change their operating
limits.
27