5
WARNING:
To avoid injury to persons or loss of life, ground each
cabinet individually to the dedicated branch circuit ground.
Connecting Main Protective Grounding Stud to the Dedicated
Branch Circuit Ground-
Connect the dedicated branch circuit ground connector to the main
protective grounding stud located inside on the back of the rear
section on the WMCM, WM, WDX, WE and inside on the side of the
15WM Series using a listed ring or closed-loop terminal.
Connecting Main Protective Grounding Stud to the Protective
Bonding Conductors-
Connect the middle wall mount frame on the WM and WD Series to
the main protective grounding stud located inside on the back of the
rear section using a listed ring or closed-loop terminal. Connect the
wall mount frame on the WE and 15WM Series to the main protective
grounding stud located inside on the back of the rear section on the
WE Series and inside on the side of the 15WM Series using a listed
ring or closed-loop terminal. Connect the front door to the grounding
stud located inside at the side of the wall mount frame using a listed
ring or closed-loop terminal.
Parts Not Bonded to Protective Earthing Terminal-
The following parts are not effectively bonded to the protective
earthing terminal: rails. If these parts need to be bonded to the
protective earthing terminal, do so in accordance with Article 250 of
the National Electrical Code.
POWER AND GROUNDING