Kayenne XL Package — Installation and Service Manual
181
Diagnostics
Diagnostics
This Information is intended for Grass Valley service personnel only!
Control Panel Module Diagnostics
Starting with Control Panel module FPGA version DS1281.037 a boot infor-
mation/diagnostic will be shown on the first character display in every
display chain (min. 1 up to max. 5).
This information (
Table 20
) is immediately visible after a power cycle and
present until the application software writes the first data to the character
displays on the module
Example codes are shows in
Table 21
Table 20. Control Panel Module Boot Display Codes
Digit
3
2
1
0
Digit Zero shows the link and FPGA boot status
*
1. Module interface link is working (normal/default).
2. FPGA was loaded over application area (normal/default).
+
1. Module interface link is working (normal/default).
2. FPGA was loaded over factory area: application area damaged, reprogramming necessary.
1. Module interface link is not working: link should come up after 1-3 seconds, if not there may be a hardware problem.
2. FPGA was loaded over application area (normal/default).
!
1. Module interface link is not working: link should come up after 1-3 seconds, if not there may be a hardware problem.
2. FPGA was loaded over factory area: application area damaged, reprogramming necessary!.
Digit 1 shows the lower number of the FPGA firmware version (DS1281.037).
Digit 2 shows the middle number of the FGPA firmware version (DS1281.037).
Digit 3 shows the upper number of the FPGA firmware version (DS1281.037) (X1 always shows “!” to see the difference to the released versions).
Table 21. Control Panel Module Boot Display Codes Examples
Digit
0
3
7
*
1. Module interface link is working (normal/default).
2. FPGA was loaded over application area (normal/default).
3. FPGA firmware version is 037 (DS1281.037).
0
3
7
+
1. Module interface link is working (normal/default).
2. FPGA was loaded over factory area: application area damaged, reprogramming necessary.
3. FPGA firmware version is 037 (DS1281.037).
0
3
7
1. Module interface link is not working: link should come up after 1-3 seconds, if not there may be a hardware problem.
2. FPGA was loaded over application area (normal/default).
3. FPGA firmware version is 037 (DS1281.037).
0
3
7
!
1. Module interface link is not working: link should come up after 1-3 seconds, if not there may be a hardware problem.
2. FPGA was loaded over factory area --> application area damaged, reprogramming necessary.
3. FPGA firmware version is 038 (DS1281.038).
!
3
5
*
1. Module interface link is working (normal/default).
2. FPGA was loaded over factory area because X1 doesn't have a application area (normal/default).
3. FPGA firmware version is X1 and 35 (DS5831.035).
!
3
5
1. Module interface link is not working: link should come up after 1-3 seconds, if not there may be a hardware problem.
2. FPGA was loaded over factory area because X1 doesn't have a application area (normal/default).
3. FPGA firmware version is X1 and 35 (DS5831.038).
Summary of Contents for Kayenne XL Package
Page 32: ...32 Kayenne XL Package Installation and Service Manual Section 1 Introduction ...
Page 62: ...62 Kayenne XL Package Installation and Service Manual Section 2 Control Surfaces ...
Page 106: ...106 Kayenne XL Package Installation and Service Manual Section 4 System Cabling ...
Page 125: ...Kayenne XL Package Installation and Service Manual 125 Software Update Figure 90 Reset Device ...
Page 185: ...Kayenne XL Package Installation and Service Manual 1 ...
Page 186: ...2 Kayenne XL Package Installation and Service Manual ...