![Grant EURFBH18MAX4 Installation, Commissioning & Maintenance Instructions Download Page 8](http://html1.mh-extra.com/html/grant/eurfbh18max4/eurfbh18max4_installation-commissioning-and-maintenance-instructions_2256727008.webp)
2.0
GRANT RESEARCH AND
DEVELOPMENT COMBUSTION AT
ALTITUDE
The R&D department of Grant Engeeniring located in Birr (Grant
Headquarters) in Ireland, are aware of the challenges of fuel oil
quality at altitude, has created an altitude chamber in its laboratory
in order to test all the burners capable of operating on territory at
any altitude.
The results allow Grant to guarantee the use of its boilers under nor-
mal conditions of use at the altitudes mentioned in Table 2.3 below.
For an even better adaptation, we are preparing kits for operation
at higher altitudes.
* For altitude adaptation of Grant vortex boilerhouse combi 52kw
and 66kw boilers, please contact us at [email protected]
2 TECHNICAL
DATA
Table 2-1:
Burner power / altitude correspondence table
Technical data
Power
Jet
Pump
pressure
Air
diffuser
adjust-
ment
Power
Jet
Pump
pressure
Air
diffuser
adjust-
ment
Power
Jet
Pump
pressure
Air
diffuser
adjust-
ment
Power
Jet
Pump
pressure
Air diffuser
adjustment
18
0.40/80°S
13
26.3
16.3
0.40/80°S
11.5
26.3
15.8
0.40/80°S
11
26.3
15.3
0.40/80°S
10
26.3
24
0.55/80°S
11
26
22
0.55/80°S
9
26
21.2
0.55/80°S
9
26
20.5
0.55/80°S
8.5
26
32
0.65/80°S
12
27.2
29.3
0.65/80°S
10.2
27.2
27.9
0.65/80°S
9.5
27.2
27.2
0.65/80°S
8.5
27.2
0-500m
500m-1000m
1000-1500m
1500-2100m
Page 8
Summary of Contents for EURFBH18MAX4
Page 2: ...Heatmax Thessaloniki Greece Phone 30 2310 383873 Fax 30 2310 383873 www heatmax gr Page 2...
Page 47: ...Product che Page 47 16 PRODUCT FICHE...
Page 49: ...Page 49 REMARKS 18 Remarks...
Page 50: ...Remarks Page 50...
Page 51: ...Remarks Page 51...
Page 52: ...HEATMAX THESSALONIKI GREECE PHONE 30 2310 383873 FAX 30 2310 383873 WWW HEATMAX GR...