10.5 REMOVING THE BURNER
To remove the burner from the boiler, proceed as follows:
- close the fuel taps upstream of the burner
- loosen the two screws (1) then slide the burner cover (2) to
remove it, taking care not to damage it.
Danger to life due to live components! Before
any intervention on the burner, use the main
switch of the system to cut off the power
supply.
DANGER
– disconnect the 7-pin plug (1) from the burner
–remove the fuel supply pipe (5) and the return pipe
(6)
2
3
- drain any fuel that may have remained inside the burner and in
the fuel supply pipe and collect it in a bowl
- loosen the clamp (7) and remove the air intake pipe (8)
7
8
– loosen the nut (9) which fi xes the burner to the boiler and, turning
the burner (10) slightly
to the right, slide it out of the boiler.
9
10
Please dispose of the oil leaving the burner in
accordance with the legislation applicable in
the country of destination. Selective sorting
of waste avoids potential damage to the
environment and human health. It also allows
many recyclable materials to be recovered,
resulting in signifi cant savings in money and
energy.
Once the burner has been removed from
the boiler, it can be placed on a rigid, level
surface. The burner should only be placed on
the fl oor if it rests on its base and should never
be turned over.
Maintenance Of Your Boiler
CAUTION
NOTE
Page 32
Summary of Contents for EURFBH18MAX4
Page 2: ...Heatmax Thessaloniki Greece Phone 30 2310 383873 Fax 30 2310 383873 www heatmax gr Page 2...
Page 47: ...Product che Page 47 16 PRODUCT FICHE...
Page 49: ...Page 49 REMARKS 18 Remarks...
Page 50: ...Remarks Page 50...
Page 51: ...Remarks Page 51...
Page 52: ...HEATMAX THESSALONIKI GREECE PHONE 30 2310 383873 FAX 30 2310 383873 WWW HEATMAX GR...