Page 14
Linear Burner Inserts Automated Operation
3.5
INSTALLING THE SUB-PANEL
Note:
Inside Mount Sub-Panel should be mounted on vertical end wall
closest to Pilot Assembly on Burner.
INSIDE MOUNT requires gas and electrical to be located inside and
at end of trough. Ignitor and ground wires must not be encased in
concrete or buried in dirt or enclosed in tight fitting conduit
OUTSIDE MOUNT requires the gas and electrical to be located
outside and at end of trough.
Outer Mount Sub Panel must be installed within 4 ft of Pilot
Assembly located at end of Burner Assembly. Grand Effects
pilot gas hose and electrical wires from Subpanel to pilot is 5 ft
maximum.
GAS INLET
GROUND
ELECTRICAL TO
PILOT IGNITOR
24 VAC FROM
CONTROL PANEL
GAS OUTLET
TO PILOT
GAS OUTLET
TO LINE BURNER
RED
GRN
GRN
GRD
RED (2)
RED (2)
GRN
4 FEET MAXIMUM LENGTH
Sub Panel Dimensions:
11.5 in W x 11.5 in H
IMPORTANT: The Sub Panel must be
located close to pilot end of burner to
connect 5 feet of wire from Sub Panel to
the pilot on the Linear Burner. Ignitor and
ground wires must not be encased in
concrete, or buried in dirt, or enclosed in
tight fitting conduit. They must be
allowed to hang freely in open air space.
Figure 7. Grand Effect
®
Sub-Panel
120 VAC
12 VAC
Control Relay or
Switch by others
Grand Effects
Control Panel
Grand Effects
Sub Panel
Flex Gas Hose by
Grand Effects
Grand Effects
Line Burner
Gas Supply
Source
Propane Adder
Hard Pipe by Others
Flex Gas Hose by
Grand Effects
Pilot Ground Wire
Pilot Spark Wire
Pilot Flex Gas Hose
Figure 8. Component Overview for Linear Inserts 3’-5’