Parameter settings in commercial program variants
Refrigerator
Extended refrigerator
Freezer
K1+
B1+
K7+
M1+
M2+
M3+
B2+
F1+
F2+
P1+
F4+
B3+
Systemvars Version number
85.75
85.75
85.75
85.75
85.75
85.75
85.75
85.75
85.75
85.75
85.75
85.75
Setpoint (celsius)
5
5
5
5
4
5
5
-18
-18
-18
-18
-18
Temperature range (celcius)
+12/+2 +12/+2 +12/+2 +12/-5
+12/-5
+12/-5
+12/-5
-5/-25
-5/-25
+10/-30 +10/-25 -5/-25
Menu access: P+1
Dry refrigeration on=H0/off=HI
dC
-
-
-
-
-
HI
-
-
-
HI
HI
-
Thaw ing on/off
UF
-
-
-
-
-
oFF
-
-
-
oFF
oFF
-
Local Alarm Limits
LAL
Upper local alarm limit (celcius)
LHL
25
25
25
25
8
25
25
25
25
25
25
25
Low er local alarm limit (celcius)
LLL
-
-
-
-
-
-
-
-
-
-
-
-
Time delay for upper alarm limit (min.)
LHd
60
60
60
60
60
60
60
60
60
60
60
60
Tiem delay for low er alarm limit (min.)
LLd
-
-
-
-
-
-
-
-
-
-
-
-
Door alarm on=1/off=0
dA
1
1
1
1
1
1
1
1
1
1
1
1
Time delay for open door (min.)
dAd
5
5
5
5
1
5
5
5
5
5
5
5
Buzzer for local alarm on=1/off=0
BU
1
1
1
1
1
1
1
1
1
1
1
1
External Alarm Limits
EAL
Upper external alarm limit (celcius)
EHL
25
25
25
25
8
25
25
25
25
25
25
25
Low er external alarm limit (celcius)
ELL
-35
-35
-35
-35
0
-35
-35
-35
-35
-35
-35
-35
Time delay for upper alarm limit (min.)
EHd
60
60
60
60
10
60
60
60
60
60
60
60
Time delay for low er alarm limit (min.)
ELd
60
60
60
60
60
60
60
60
60
60
60
60
Door alarm on=1/off=0
dA
-
-
-
-
-
-
-
-
-
-
-
-
Time delay for open door (min.)
dAd -
-
-
-
-
-
-
-
-
-
-
-
Buzzer for local alarm on=1/off=0
BU
-
-
-
-
-
-
-
-
-
-
-
-
Calibration of sensor
cAL
Offset adjustment sensor A (kelvin)
cA
0
0
0
0
0
0
0
0
0
0
0
0
Offset adjustment sensor E (kelvin)
cE
-
-
-
-
-
-
-
-
-
0 -
-
Offset adjustment sensor F (kelvin)
cF
-
-
-
-
-
-
-
-
-
-
-
-
Frost Protection
FP
Activation of frost protection On=1/Off=0
Act
-
-
-
-
-
-
-
-
-
-
-
-
Test of frost protection
tES
-
-
-
-
-
-
-
-
-
-
-
-
Setpoint of frost protection (celcius)
SEt
-
-
-
-
-
-
-
-
-
-
-
-
Display of current sensor temperaturer (celcius)
PrE
-
-
-
-
-
-
-
-
-
-
-
-
Fixed or escorting alarm limits (FAS - ESC)
ALL
FAS
FAS
FAS
FAS
FAS
FAS
FAS
FAS
FAS
FAS
FAS
FAS
Soft chilling (soft-chill)
SCL
-
-
-
-
-
-
-
-
-
-8 -
-
Hard chilling (hard-chill)
HCL
-
-
-
-
-
-
-
-
-
3.00
-
-
Time controlled chilling (timed-chill)
PCL
-
-
-
-
-
-
-
-
-
-18 -
-
Number of defrosts / 24h
4
4
4
4
4
4
4
4
4
4
4
4
Selected sensor display
dPS
-
-
-
-
-
-
-
-
-
-
-
-
Alarm & presentation
Alarm settings
A
Condenser monitoring alarm on (celcius)
A1
65
65
65
65
65
65
65
65
65
65
65
65
Condenser monitoring alarm off (celcius)
A2
40
40
40
40
40
40
40
40
40
40
40
40
Genindtrædelses tiden for akustisk alarm (min.)
A3
5
5
5
5
5
5
5
5
5
5
5
5
Alarm history on=1/off=0
A4
-
-
-
-
-
-
-
-
-
-
-
-
Selection of sensor for alarm system
A5
-
-
-
-
-
-
-
-
-
-
-
-
Mulige valg af følere til alarm system
-
-
-
-
-
-
-
-
-
-
-
-
Præsentation af temperatur
P
Temperature display hold after defrost
P1
30
30
30
30
30
30
30
30
30
30
30
30
Temperature display hold during normal operation
P2
3
3
3
3
3
3
3
3
3
3
3
3
Display updating frequency (sec)
P3
10
10
10
10
10
10
10
10
10
10
10
10
Temperature display, Celsius or Fahrenheit
P4
C
C
C
C
C
C
C
C
C
C
C
C
System setup
Compressor settings
C
Differential for compressor start and stop (kelvin)
C1
5
5
5
5
4
5
5
5
5
5
5
5
Max. allow ed setpoint (celcius)
C2
12
12
12
12
12
12
12
-5
-5
10
10
-5
Min. allow ed setpoint (celcius)
C3
2
2
2
-5
-5
-5
-5
-25
-25
-30
-25
-25
Compulsory compressor pause time (min.)
C4
5
5
5
5
5
5
5
5
5
5
5
5
No. of sensors for condenser monitoring
C5
1
1
1
1
2
1
1
1
2
1
1
1
Door open time before compressor stops (min.)
C6
1
1
1
1
1
1
1
1
1
1
1
1
Soft differential for cool/heat cut-out (kelvin)
C7
-
-
-
-
-
-
-
-
-
-
-
-
Setpoint for condenser fan
C8
-
35 -
-
-
-
35 -
-
-
-
35
Cut-out differential for condenser fan (kelvin)
C9
-
5 -
-
-
-
5 -
-
-
-
5
Evaporator fan settings
F
Evap.fan start after defrost, and during dry refrig. (celcius)
F1
-
-1 -
-1
-1
-3
-1
-1
-1
-1
-1
-1
Evap.fan pause time at compressor stop (min.)
F2
5
0
5
5
5
5
0
5
5
5
5
0
Ford. vent. køretid ved kompressor stop (sek.)
F3
60
60
60
60
60
60
60
60
60
60
60
60
Stop temp. of LT kompressor ic cascade evaporator (celcius)
F4
-
-
-
-
-
-
-
-
-
-
-
-
Defrost settings
d
Number of defrosts / 24h
d1
4
4
4
4
4
4
4
4
4
4
4
4
Stop temperature in evaporator during defrost (celcius)
d2
7
4
7
4
7
4
4
4
4
12
4
4
Defrosting on/off = (0/1) at pow er up first time
d3
0
0
0
0
0
0
0
0
0
0
0
0
Max allow ed defrosting time (min.)
d4
30
30
30
30
30
30
30
30
30
30
30
30
Defrosting mode (1=automatic, 2=air, 3=electrical)
d5
2
3
2
1
3
1
3
3
3
3
3
3
Drip time after defrost stop (min.)
d6
0
4
0
4
0
4
4
4
4
2
4
4
Limit for automatic defrosting mode (celcius)
d7
2
2
2
4
2
4
2
4
4
4
4
4
Evaporator monitoring (celcius)
d8
-35
-35
-35
-35
-35
-35
-35
-35
-35
-40
-35
-35
Defrost after chilling stop
d9
-
-
-
-
-
-
-
-
-
1 -
-