All electrical wiring in the hazardous area must be
encased in Class I, Division I, Group D approved
explosion-proof conduit. Follow all National, State,
and Local electric codes.
A conduit seal (D) is required within 18 in. (457 mm)
of the motor for the US and Canada. See Fig. 3.
All cables must be rated at 70°C (158°F).
Flame
Flame
Flame Proof
Proof
Proof (ATEX)
(ATEX)
(ATEX)
Use appropriate conduit, connectors, and cable
glands rated for ATEX II 2 G. Follow all National,
State, and Local electric codes.
All cable glands and cables must be rated at 70°C
(158°F).
Typical
Typical
Typical Installation
Installation
Installation
NON
NON
NON---HAZARDOUS
HAZARDOUS
HAZARDOUS AREA
AREA
AREA
HAZARDOUS
HAZARDOUS
HAZARDOUS AREA
AREA
AREA
Figure 1 Typical Installation
Key
Key
Key for
for
for Fig.
Fig.
Fig. 1
1
1
A
Electrical Supply (must be sealed conduit
approved for use in hazardous locations)
B
Disconnect, with lock
C
Start/Stop Control (must be approved for
use in hazardous locations)
D
Explosion Proof Conduit Seal. Required
within 18 in. (457 mm) of the motor for the
US and Canada.
Key
Key
Key for
for
for Fig.
Fig.
Fig. 1
1
1
E
Fluid Pressure Gauge
F
Fluid Shutoff Valve
G
Pump Ground Wire. Two ground terminals
are provided if local code requires redundant
grounding connections.
H
Fluid Drain/Pressure Relief Valve
8