background image

General Feature Information

313903B

11

General Feature Information

Tachometer 

Displays actual engine/compressor shaft speed (RPM). 
A flashing asterisk indicates the tachometer is enabled.

A second LCD line displays the normal target operating 
speed.

An ON/OFF indication displays to indicate when alarm 
monitoring is active.

It is possible to override the active alarms when the 
tachometer is enabled and drive mechanism is operat-
ing a minimal speed, by pressing the 

RST/CLR

 button 

until the machine accelerates to 50% of it’s normal oper-
ating speed. At that point, the alarm override ceases, 
allowing proportional alarmed startup of the equipment. 

Enabled alarms stay active through all ranges of input 
rpm until they are manually reset after the machine has 
decelerated from 50% of its normal operating speed.

NOTE: When the alarm override is active, a letter “T” 
and the word “OFF” will be displayed on the LCD.

When the 

RST/CLR

 button is pushed to reset Sentinel 

II, the display resets back to 0 (zero). However, if the dis-
play is in the totalized mode (identified by the letter “T”) 
pressing 

RST/CLR

 resets the totals back to the last 

stored value. Care should be taken when resetting a 
fault to ensure that the display is not in the totalized 
mode. Resetting the fault will also reset the total accu-
mulated usage.

Zone Enable/Disable 

Zones are enabled during programming. A zone may be 
disabled initially by programming the zone “OFF” or by 
temporarily placing an enabled zone in “BYPASS” mode 
(Terminals 29, 30, 31 and 32). 

Closing the contacts for “ZONE BYPASS” disables a 
zone from any fault time-outs. The zone display shows 
the word “BYPASS” to indicate this condition. 

When the bypass has been removed, active monitoring 
of the zone continues. If the alarm is enabled, the alarm 
time-out will restart.

Fault Relay

There are three fault relays. One is used as a Power 
Monitor and two are used as Zone Fault relays. 

The Power Monitor Relay is a single-pole, double-throw 
relay with Form C contacts. It energizes approximately 5 
seconds after power is applied and stays energized as 
long as power is available to the monitor. When power is 
removed from the system, the relay deenergizes imme-
diately.

Zone Fault Relays are enabled during programming. 
Each Zone Fault Relay is a double-pole, double-throw 
relay with two Form C contacts that change state when 
their associated zone goes into fault. The Zone Fault 
Relay may be programmed to either pick or drop when a 
fault is detected, allowing for fail-safe operating if 
desired. 

A system fault TTL output is also available to annunciate 
faults. It is linked with programming for relay energiza-
tion settings.

Resetting Faults

Faults may be reset in several ways:

Manually reset at the monitor by pressing the 

RST/CLR

 button. 

Using the “Safety Set” target (see Safety Set, 
page 8).

Electrically by closing the remote reset contacts.

Serial Port commands (see Serial Communica-
tion, page 9).

Summary of Contents for 562870

Page 1: ...for use in explosive atmospheres Part No 562871 Includes Explosion Proof Enclosure See Technical Data page 26 for model information including power requirements Important Safety Instructions Read all warnings and instructions in this manual Save these instructions ti14387 ti14386 Model 562870 Model 562871 Bulletin 44701 555840 EN ...

Page 2: ...ons EQUIPMENT MISUSE HAZARD Misuse can cause death or serious injury Do not operate the unit when fatigued or under the influence of drugs or alcohol Do not exceed the maximum working pressure or temperature rating of the lowest rated system com ponent See Technical Data in all equipment manuals Do not leave the work area while equipment is energized or under pressure Turn off all equipment and fo...

Page 3: ...al interference If the installation is in an area of high electrical noise interference or in trays with other control wiring a shielded cable pair is recommended Shielded cable should be used on applications where engines or heavy duty motors are in close proximity to the monitor wiring or sensors If shield cable is used the shield should stay intact as close to the termination screws as possible...

Page 4: ...o install the Lube Sentinel II Monitor in your lubrication system All electrical connections are made to terminals along both sides and the bottom of the main circuit board except for serial communications Serial communication connections are made via a special plug in header block External Connection Terminals FIG 1 ...

Page 5: ...o these contacts Contacts are rated 0 5 ampere at 125VAC and 1 0 ampere at 30VDC The relays may be programmed to either energize or deenergize during a fault See FIG 3 Terminals Power Connection 1 2 115 230 VAC power input terminals polarity insensitive 3 Earth Ground 4 24 VDC Input 5 0 VDC Input 6 24 VDC Out for sensor use 7 0 VDC Out for sensor use 8 0 VDC Out for sensor use FIG 2 FIG 3 Examples...

Page 6: ... as for Zone 1 Pole A for Zone 2 uses terminals 15 nc 16 com and 17 no Pole B for Zone 2 uses terminals 18 nc 19 com and 20 no See FIG 4 FIG 4 Wiring Examples when Zone 1 and Zone 2 are used Ignition Shutdown Magneto Grounding External Flow No Flow Lights Energize External Load relay coil etc ...

Page 7: ... contacts 21 nc 22 com and 23 no This relay will be ener gized as long as power supply voltage is active FIG 5 Terminal Strip Left Side Bottom Sensor Inputs FIG 5 Power Failure Relay Connections Terminals Sensor Inputs 25 26 For Factory Use 27 28 Tachometer Input 29 30 Bypass Zone 2 31 32 Bypass Zone 1 33 34 Reset Alarm 35 36 Cycle Switch Zone 2 37 38 Cycle Switch Zone 1 FIG 6 Typical Input Device...

Page 8: ...at allows the opera tor to manually activate the function buttons from out side the enclosure 1 Disconnect all power to the monitor 2 Verify that the module is properly aligned and all pins are in their proper sockets 3 Place the magnetic Datawand over the Safety Set target above the desired button to activate the func tion buttons FIG 8 The Datawand activates the sensor through the win dow and ke...

Page 9: ...a write to verify the proper action has taken place NOTE Changes made through the serial link are active but not permanent until the save to E2 command WC is issued If the WC command is not issued turning the power off and on restores the originally saved operating parameters See page 26 for recommended user sup plied communication port connectors Serial Communication Wiring The Serial Communicati...

Page 10: ...when the switch is closed LCD Display G Displays information in one of three ways Any of these can be selected by pressing the SLCT button B The LCD displays letter codes to identify the chosen display I Instantaneous Displays the lube displacement over a 24 hour period based on the time interval between the last two cycles of the divider valve This time and the amount of lube delivered by one cyc...

Page 11: ...programming A zone may be disabled initially by programming the zone OFF or by temporarily placing an enabled zone in BYPASS mode Terminals 29 30 31 and 32 Closing the contacts for ZONE BYPASS disables a zone from any fault time outs The zone display shows the word BYPASS to indicate this condition When the bypass has been removed active monitoring of the zone continues If the alarm is enabled the...

Page 12: ...age 4 Programming the Lube Sentinel II Monitor Operation of the Lube Sentinel II is controlled through three buttons located on the front display panel Buttons are labeled RST CLR reset and or clear SLCT select PGRM program After the Lube Sentinel is programmed it is ready for normal operation in the monitor mode In this mode the Lube Sentinel II monitors the lubricant delivery and pro vides assoc...

Page 13: ... SLCT button to change to YES 3 Then press the PRGM button NOTE Pressing any other button when NO is showing will erase any changes indicated and leave all settings as they were before entering the programming function FIG 11 RST CLR SLCT PRGM Press PRGM button to enter programming field Press SLCT button to toggle between four fields CONFIGURATION CONFIGURATION SERIAL PORT GLOBAL SETTINGS 1 2 ENABL...

Page 14: ...unts a Press the SLCT button to toggle between the displayable units b When choice displays on screen push PGRM button to advance to the next pro gramming option NOTE Each zone can read out in different units Port Total The total quantity of lubricant vol ume provided to lubrication points This input is necessary for calibrating the Senti nel II for the lubricant volume required for one cycle of t...

Page 15: ...us of one alarm zone will auto matically change the status of the other zone b When choice displays press the PGRM but ton to advance to the next programming option Flow Alarm On Choose one LOW FLOW HIGH FLOW or HI and LOW FLOW alarms a Press the SLCT button to toggle between choices b When choice displays press the PGRM but ton to advance to the next programming option Low Flow Set Appears if LOW...

Page 16: ...n to advance to the next programming option Enable Tach Choose one YES or NO a Press the SLCT button to toggle between choices If the tachometer is not to be enabled select NO No further options will be asked for the zone Enabling the tachometer selecting YES will add a plus sign to the display screen to indicate that alarm times are being adjusted FIG 16 NOTE The plus sign also appears if Faults ...

Page 17: ... maximum adjusted values are 50 45 pints at 150 rpm and 15 pints at 50 rpm c Press the PGRM button Since there are no additional options the display returns to the start of the CONFIGURATION ZONE1 selec tion 3 Push the SLCT button to toggle to CONFIGURA TION ZONE2 NOTE Pressing RST CLR at this time exits the pro gramming mode and asks if the changes made should be permanent Use the SLCT button to ...

Page 18: ... programming option Invert Relays fault relay logic Allows selection of whether the zone fault relays and the TTL output will energize or deenergize when a fault is registered Choose either YES or NO a Press the SLCT button to toggle between choices NO The fault relay contacts will be deener gized during normal system operation and energize upon a fault YES The fault relay contacts will be ener gi...

Page 19: ...he monitor mode and updated with the new saved changes NOTE Pressing any other button or leaving the response set to NO erases and does NOT save changes Sentinel II returns to the original setup configuration Once the changes have been saved pressing RST CLR button will not undo the new setup config uration ...

Page 20: ...eter is enabled f INTEGER Block Total g INTEGER Low Flow Limit for Alarm h INTEGER High Flow Limit for Alarm i INTEGER Tachometer Setting for Normal RPM j BYTE Tach Pulses per RPM R2z Read the current status of Zone 1 or 2 The z is set to either 1 or 2 The returned message is a data structure arranged in the following order a BYTE Cycle Position Indicates if the input is opened or closed 0 or 1 b ...

Page 21: ...ing addressed b BYTE x Alarm generation 0 Low Flow Alarm Only 1 High Flow Alarm Only 2 Both Low and High Flow Alarms W5zx BYTE Turns the Tachometer On or Off 0 Disabled 1 Enabled W6zxxxx Set the port total a BYTE z 1 or 2 for the zone being addressed b INTEGER xxxx 5 to 9999 thousandths of a cu in W7zxxxx Set Low Flow Alarm a BYTE z 1 or 2 for the zone being addressed b INTEGER xxxx 5 to 65535 per...

Page 22: ...aults WC Save Data to EEPROM Programming changes become permanent WDx Set the fault count to alarm on where x 1 2 or 3 WEx Set the polarity of the fault relays 0 No Relays not inverted normally deenergized energize on a fault 1 Yes Relays are inverted normally energized deenergize on a fault ...

Page 23: ...903B 23 Dimensions JIC Model 562870 FIG 17 0 5 in 12 7 mm 0 62 in 15 9 mm 6 25 in 158 7 mm 5 00 in 127 0 mm 4 00 in 101 6 mm 8 75 in 222 2 mm 8 25 in 209 5 mm 0 25 in 6 3 mm 0 312 in 7 9 mm Diameter 9 50 in 241 3 mm ...

Page 24: ...Dimensions 24 313903B Model 562870 FIG 18 5 37 in 136 5 mm 0 87 in 22 2 mm Diameter conduit connection 2 each side ti14405 ...

Page 25: ...ons 313903B 25 Model 562871 FIG 19 6 875 in 174 6 mm 8 5 in 215 9 mm 7 75 in 196 9 mm 6 00 in 152 4 mm 0 875 in 22 2 mm 0 813 in 20 6 mm FIG 20 6 5 in 165 1 mm 1 2 N P T conduit con nection 2 each side ti14406 ...

Page 26: ... 500 or equivalent Proximity Switch Pulse Inputs 24VDC 12 ma each Tach Sensor Pulse Input 24VDC 12 ma Zone Bypass and Alarm Inputs 24VDC 12 ma each Relay Outputs Contact Ratings Rated Load 0 5Amp at 125VAC 1Amp at 30VDC Maximum Carry Current 2Amp Maximum Operating Voltage 250VAC 220VDC Maximum Switching Capacity 62 5 VA 60W Minimum Permissible Load 10µA 10mVDC Relay Coil Current Consumption 70ma 1...

Page 27: ...Notes 313903B 27 Notes ...

Page 28: ... defect in material or workmanship repairs will be made at a reasonable charge which charges may include the costs of parts labor and transportation THIS WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ANY OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE Graco s sole obligation and buyer s sole remedy for any breac...

Reviews: