background image

312864B

Instructions - Parts

Communications
Gateway Module

For use with Graco Control Architecture based systems to provide fieldbus
communications capabilities.

Important Safety Instructions

Read all warnings and instructions in the system
operation manual. Save these instructions.

TI11985A

4003764

Conforms to

UL Std. 508

Certified to CAN/CSA Std.

C22.2 No. 14

Summary of Contents for 312864B

Page 1: ...ntrol Architecture based systems to provide fieldbus communications capabilities Important Safety Instructions Read all warnings and instructions in the system operation manual Save these instructions...

Page 2: ...l Data 11 Graco Standard Warranty 12 Graco Information 12 Models To order replacement parts see Parts on page 11 To order installation kits for a Graco Control Architecture based system see the system...

Page 3: ...ector D Module Connection Screws E Access Cover F Module Status LEDs G Fieldbus Status LEDs see descriptions on page 6 H CAN Connectors FIG 1 TI11985A TI11814A TI11815A TI11816A A D C see Fieldbus Con...

Page 4: ...your sys tem and reinstall token If fails order new token Module Requirements Power Supply The CGM requires a 12 30 VDC 0 2 A power supply Refer to the system manual for system level power sup ply gu...

Page 5: ...E 3 Insert and press map token T firmly into slot 4 Press and hold the map upload push button M for three seconds The red LED L will flash twice pause and repeat once after the data map is suc cessfu...

Page 6: ...cription Comments Off Not initialized No power or module in SETUP or NW_INIT state Green Normal operation Diagnostic event s present Flashing Green Initialized diagnostic event s present Used by engin...

Page 7: ...en On line one or more connections established CIP Class 1 or 3 Flashing Green On line no connections established Red Duplicate IP address FATAL error Flashing Red One or more connections timed out CI...

Page 8: ...e Flashing Red 1 Hz One or more connections timed out Alternating Red Green Self test State Description Off No power or not initialized Green Initialized Flashing Green 1 Hz Missing or incomplete conf...

Page 9: ...Configuration error State Description Off No power or not initialized Green Initialized Flashing Green Initialized diagnostic event s present Red Exception error Pin Signal Description 1 2 3 B Line P...

Page 10: ...sh a code pause then repeat Module Status LED Signal Diagnosis Solution Red 7 flashes Data map load failure Verify that you are using the correct token for your system type and rein stall token If ins...

Page 11: ...et CGMDN0 only 1 15V760 MODULE Gateway EtherNet IP CGMEP0 only 1 15V761 MODULE Gateway PROFIBUS CGMPB0 only 1 15V762 MODULE Gateway PROFINET CGMPN0 only 1 B 289697 Base 1 D 114135 SCREW mounting modul...

Page 12: ...y include the costs of parts labor and transportation THIS WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ANY OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR W...

Reviews: