Operation
18
3A7031A
Alarm Types
Alarm ID
Alarm Type Alarm Icon
Cause
Solution
A13
Level Empty
There is a low
lubricant level
Fill the reservoir.
A11
Cycle
Timeout
The time out
expired before
receiving
programmed
number of cycle
counts.
Inspect the lubrication system for broken or
plugged lines.
Confirm that the pump is operating correctly.
Inspect the cycle and proximity switch and
wiring.
Confirm that sufficient time was programmed
for the environmental conditions (e.g. slow
system response in cold temperatures).
Confirm that the programming is correct.
A15
Pressure
Timeout
The time out
expired prior to
receiving pressure
switch input.
Inspect the lubrication system for broken or
plugged lines.
Confirm that the pump is operating correctly.
Confirm that the vent valve is operating
correctly
Inspect the wiring, pressure, switch, and
sensor.
Confirm that sufficient time was programmed
for the environmental conditions (e.g. slow
system response in cold temperatures).
Confirm that the programming is correct.
A16
Pressure
not vented
The vent valve
failed to relieve
power to the
system.
Fix the cabling to the vent valve.
Ensure that enough power is being delivered
to the vent valve.
Confirm that the controller settings are correct.
Inspect the wiring, pressure switch and
sensor, and check for short circuits.
Replace the vent valve if it is broken.
A19 (Pin 2)
A20 (Pin 1)
A21 (Pin 4)
A22 (Pin 5)
Output
Overcurrent
Output load is
drawing too much
current
Inspect the wiring.
Confirm that the pump is operating correctly
and not drawing more current than expected.