INSTALLATION
Before installing your meter, review the
safety instructions given above� Exam-
ine your meter to make sure there are
no visible signs of shipment damage�
Plan your meter installation by review-
ing the following procedures� Your sys-
tem must be mounted on a vented tank�
If the tank is unvented, your local dealer
or distributor can supply a pressure cap�
If the meter is located in a rigid piping
system where the fluid is trapped (for
example, by gravity, valves or nozzles)
thermal expansion of the fluid can
create pressure spikes that can damage
a meter�
Install a thermal relief valve or otherwise
allow for thermal expansion of the fluid.
Prior to installation, determine the fitting
angle desired and whether horizontal or
vertical orientation is required�
Rotate Fittings
To rotate inlet and/or outlet fittings,
remove the two nuts and bolts that
secure each fitting. Rotate the fitting to
the desired orientation� Make sure the
O-ring is fully seated� Tighten the nuts
and bolts snugly�
Change Orientation
1� Pull the knob to remove from unit�
Remove screws that hold bezel in
place and set aside�
2� Remove the two screws that hold
the faceplate in place and remove
faceplate. (Figure 1)
3� Remove two screws to release
the counter assembly. (Figure 2)
4� Remove the bevel gear from the
center of the coverplate� Remove
the eight pairs of nuts and bolts
that hold the coverplate assembly
in place�
5� Now you can rotate the coverplate
t o t h e d e s i r e d o r i e n t a t i o n �
Reassemble in reverse order,
making sure the O-ring is fully
seated� Torque eight nuts and bolts
to 60 - 72 in-lb�
Meter Installation
1� Remove protective plugs from the
meter inlet and outlet ports�
2� Wrap threaded male connections
with thread tape or use a pipe
sealant compound compatible with
petroleum fuels� We recommend
thread sealant at the inlet fitting in
horizontal orientation�
3� Install the meter on the pump using
an appropriately sized nipple� The
meter’s flow path is marked on the
housing exterior with an arrow point-
ing toward the outlet port�
4� Install other system components on
the meter and tighten snugly�
OPERATION
A L W AY S F O L L O W S A F E T Y
PRECAUTIONS WHEN OPERATING
THIS EQUIPMENT. REVIEW THE
SAFETY INSTRUCTIONS.
Before
each use, visually check the meter to
ensure it is securely connected to other
system components and there is no
leakage� Promptly wipe spilled fuel from
the meter’s exterior and other system
components�