
9
DEFINITIONS OF MENU PROMPTS
The following is a list of abbreviations as they appear on the display and front panel of the unit.
ABBREVIATION
DESCRIPTION
PRE B
PRESET B - This is the setpoint for Relay B. Preset B can be used as a Prewarn or Grand/Batch Total
alarm.
FACTOR
SCALING FACTOR - This portion of the menu is used to set the 5 digit dividing scale factor for the count
input.
DP F A
DECIMAL POINT FOR FACTOR A - Enter location of decimal point for scaling Factor A by pressing the
button under the digit where the decimal is desired.
COUNT
PORTION OF MENU FOR SETTING COUNTER VARIABLES
RST 0
RESET TO 0 - Counter will reset to 0. The Batcher will count up from 0.
SET PR
SET TO PRESET - Counter will reset to preset A. The Batcher will count down from preset A.
DP LOC
DECIMAL POINT LOCATION - Enter desired location of decimal by pushing the button under the digit
where the decimal is desired. Changing the decimal will change the decimal location in the counter's
presets and rate display.
gr tot
GRAND TOTAL- This sets the second counter to count the Grand Total.
ba tot
BATCH TOTAL- This sets the second counter to count the number of Batches.
HI CPS
HIGH COUNTS PER SECOND - This sets the unit for high count speeds (0-9.99 kHz)
LO CPS
LOW COUNTS PER SECOND – This sets the unit for contact debounce filtering (0-40 Hz)
RATE
PORTION OF MENU FOR SETTING RATE VARIABLES
sec
SECONDS - The rate display will read in rate per second.
mins
MINUTES- The rate display will read in rate per minute.
hours
HOURS - The rate display will read in rate per hour.
NOR##
NORMALIZING FACTOR - Normalizes (averages) the data being received. Higher settings provide more
normalizing (averaging) for a more stable display. Derived from the equation:
(Old Data x "NOR" + New Data)
("NOR" + 1)
FIGUR ##
SIGNIFICANT FIGURE - This sets the amount (1-5) of meaningful figures the unit will display. (RATE DIS
PLAY ONLY). FOR EXAMPLE: If "2" is set as the figure, a rate of 273.45 will be displayed as 270.