9
8: DIAGRAMS
(continued)
Typical Motor Nameplate Showing Service Factor Amps (SF AMPS)
8: DIAGRAMS
Labels found on the Controller Access Cover:
In this example, use the 4.2 Amp setting indicated on the Motor Overload Setting Table. This setting is used to account
for any voltage fluctuation.
Service Factor Amps (SF AMPS)
that are used to set the Motor
Overload Setting Switches.
Motor Overload Setting Label
Use this label to choose the correct Motor Overload Switch
Setting. This label is found under the controller access cover.
Status Code
Label
Use this label
to diagnose any
system errors.
This label is
found on the
side of the
controller
access cover.
Motor Overload Setting
WARNING
Disconnect Power And Wait For LED Indicator To Turn
Off Before Touching Motor Overload Setting Switches.
1 = UP 0 = DOWN
DIP Switch Setting
Motor Overload Setting (Amps)
1 2 3 4
1AB2
2AB2
1 1 1 1
2.5
4.6
1 1 1 0
2.8
5.2
1 1 0 1
3.3
5.3
1 0 1 1
3.5
5.8
0 1 1 1
3.8
6.5
0 0 0 0
4.2
6.9
Status Codes*
Green Light Codes
Constant
Standby/Low Voltage
Blinking
Pump Running
Red Light Codes
Constant
Replace Controller
1 Blink
No Water/Loss Of Prime
2 Blinks
Tank Water-Logged
3 Blinks
Pressure Sensor Fault
4 Blinks
Pump or Motor Bound
5 Blinks
Short Circuit
6 Blinks
Ground Fault
7 Blinks
High Temperature
8 Blinks
Over Voltage (>264V)
9 Blinks
Motor Overload
*No Light - No/Very Low Voltage
Application Type Switch Setting
WARNING
DIP Switch Setting
1 = UP 0 = DOWN
1 2 3 4
Minimum Speed (Hz)
Ramp Setting
1 1 1 1 *
10
Slow
1 1 1 0 *
10
Medium
1 1 0 1 *
10
Fast
1 0 1 1
30
Slow
0 1 1 1
30
Medium
0 0 0 0
30
Fast
*THESE SETTINGS ARE NOT TO BE USED WITH SUBMERSIBLE PUMPS.
Disconnect Power And Wait For LED Indicator To Turn
Off Before Touching Application Setting Switches.
Application Switch Setting Label
Use this label to choose the correct
Application Switch Setting. This label is
found under the controller access cover.
Diagram 5
Diagram 6