GMC-I Messtechnik GmbH
29
4.6
Configuring the S0 Pulse Outputs
p r o g
p u l s
P
p u l s
e n e r
y1
1 m p .H
g
P
Wh
p u l s
e n e r
y 2
g
P
p u l s
r a t e
10
1
P
kWh
Interface Menu ...
Source for pulse output 1
Source, pulse output 1:
collective energy (4L)
Pulse output 1
Pulse rate
10 pulses / kWh
Pulse output 2:
same as pulse output 1
: Value Settings
1 ... 5000 pulses / kWh (MWh)
or kVArh (MWArh)
Resolution:
1 pulse if rate < 1000
10 pulses if rate
1000
T3
p u l s
P
T1: Source Selection
L1, L2, L3,
T2: Quantity Selection
Active/reactive energy
kWh, kVArh,
Mwh, MVArh
: Value Settings
Pulse outputs
Pulse length
0.1 s
: Value Settings
0.1 s ... 0.8 s
P
brief
T3
P
brief
storage to memory
no storage to memory
storage to memory
P
long
Menu
Display
Time
2 minutes
= import, low tariff;
= import, high tariff,
Import energy from the system (positive sign)
= export, low tariff;
= export, high tariff,
Export energy to the system (negative sign)
1 M p. L
1 M p. H
+
0
.
1 s
leng
h
t
E x p. H
E x p. L
The import and export settings are without significance for reactive energy, which is always indicated with a positive
value.